50-660 Kotron
®
Model 805 Smart RF Level Transmitter
16
Display
Action
Comment
1
2
3
4
5
6
7
8
9
10
11
12
13
*Level*
*%Output*
*Loop*
Transmitter Display
Transmitter default display.
Level, % output,
and
Loop
values cycle every 5 seconds (two seconds each value).
Transmitter Display
Level measurement in cm or in.
Transmitter Display
Level as percentage of loop current (20 mA) span.
Transmitter Display
Loop current output.
Select
units for level
lu =
cm
or
in.
measurement display.
Enter
level value for the
Use Up and Down keys to set reading to present level of
lower calibration point.
medium in vessel. See
Section 1.4
.
Transmitter Display
Measured capacitance at low calibration point.
Enter
level value for the
Move the level in the tank. Use Up and Down keys to set
higher calibration point.
reading to present level of medium in vessel. See
Section 1.4
.
Transmitter Display
Measured capacitance at high calibration point.
Enter
the level value for the
Use Up and Down keys to set reading to level corresponding
4 mA point.
to 4 mA loop current.
Enter
the level value for the
Use Up and Down keys to set reading to level corresponding
20 mA point.
to 20 mA loop current.
Enter
damping factor.
Choose the damping factor (1–45 sec) for smoothing the
level/output/loop displays.
Enter
the desired loop current
Select
22 mA, 3.6 mA
or
Hold.
(3.6 mA is not valid if unit
in presence of a fault.
includes
both
digital display and HART)
Enter
HART poll address.
Select
a HART poll address (0–15). Enter 0 for a single
transmitter installation.
Trim loop current to 4.00 mA.
With a meter in the loop, use Up and Down keys to adjust
current to 4.00 mA.
Trim loop current to 20.00 mA.
With a meter in the loop, use Up and Down keys to adjust
current to 20.00 mA.
Enter test value of loop current
Use Up and Down keys to set loop current to a desired value
(3.5–22.0 mA) for testing.
Transmitter Display
Measured capacitance at present level of medium in vessel.
Transmitter Display
Internal timing count with known capacitance in circuit
(factory diagnostic).
Transmitter Display
Internal timing count with probe disconnected (factory
diagnostic).
Transmitter Display
Internal timing count at present level of medium in vessel
(factory diagnostic).
Select
Yes to reinitialize
Resets all configuration parameters to factory default
all values
values.
Transmitter Display
Shows version number of firmware.
Enter new password
Use Up and Down keys to select desired value (0–255).
Level
xx.x lu
%Output
xx.x%
Loop
xx.xx mA
Units
lu
Lo Cal
xxx.x lu
Lo Cap
xxxx pF
Hi Cal
xxx.x lu
Hi Cap
xxxx pF
Set 4mA
xxx.x lu
Set 20mA
xxx.x lu
Damping
xx sec
Fault
Choice
Poll Adr
xx
Trim 4
xxx
Trim 20
xxxx
14
15
16
17
18
Loop Tst
xx.x mA
Prb Rdg
xxxx pF
19
20
Osc Tst
xxxx tk
Opn Prb
xxxx tk
21
22
# Ticks
xxxxx tk
Reinit
xx
23
24
Ver n.nAa
New Pass
xxx