2013 Magnum Energy, Inc.
Page 28
Installation
2.7.3
Inverter Warning Label
A warning label as shown in Figure 2-15 is provided to inform all personnel that an inverter is
installed in your electrical system. Af
fi
x this label in a clearly visible location at the electrical panel
that is being powered by the inverter. This is because it might be falsely assumed that the panel is
no longer “hot” after the AC power has been shut off, when power may actually still be available
due to the inverter automatically powering the panel.
Figure 2-15, Warning Label
2.8 Final
Inspection
1. Verify all cables/conduit runs are secured with wire ties or other non-conductive fasteners to
prevent cha
fi
ng or damage from movement and vibration.
2. Verify strain reliefs or grommets are in place to prevent damage to the wiring or conduit where
it passes through walls, bulkheads, or other openings.
3. Verify all AC connections are correct and torqued to a maximum of 32 in lbf (3.6 N-m).
4. Replace the covers on the main electrical/distribution panel.
5. Replace the chassis access cover.
6. Verify the inverter’s front panel switch is in the “OFF” position.
Info
: If required by code, have the installation inspected by an electrical inspector.
This electrical system is equipped with an Automatic
Generator Starting (AGS) device and/or an inverter.
Disconnect all AC and DC power to the AGS and/
or inverter before performing any service to the
electrical system. Failure to do so can result in shock
causing serious injury or death.
PN: 62-0002 Rev A