10
2.0 Installation
Figure 2-6, Generator Run Sense Options
Option 3 – Use an external 120VAC coiled relay to bring the generator 's battery voltage to
the AGS run sense port (AGS Terminal Block Port #2) only while the generator is running .
The generator’s battery voltage must be 10 to 40 VDC.
1 2 0V A C C o il R e la y
On Generator
NC
COM
NEU
HOT
NO
120VAC Outlet
Inside Generator
Generator
Battery
negat
iv
e
run s
ens
e
A G S T erm inal B loc k P orts :
1
2
3
4
5
6
7
8
D C F us e
(5A m ax )
Option 1 - Tap into the positive side of the generator’s hour meter or running light ; ensure
the voltage is 10 to 40 VDC only while the generator is running .
Generator
Battery
Inside Generator
Ge n e ra to r
R u n n in g L a m p
OR
Ge n e ra to r
H o u r M e te r
0
1
2
3
ne
ga
tiv
e
D C F us e
(5A m ax)
ru
n s
en
se
A G S T erm inal B loc k P orts :
1
2
3
4
5
6
7
8
Option 2 - Use a 120VAC to 12VDC step -down transformer (normally used to charge power
equipment batteries ) and plug into the generator’s 120VAC output. The step-down
transformer provides 12 VDC output only while the generator is running .
ne
gat
iv
e
D C F us e
(5 A m ax)
ru
n s
ens
e
A G S T erm inal B loc k P orts :
1
2
3
4
5
6
7
8
On Generator
120VAC Outlet
120 VAC IN
12 VD C OU T
T R AN SF OR M ER
What if my generator does not have a run sense output? If your gen-
erator is not equipped with a generator run sense output, review Figure 2-6
for alternative options.
Option 3 – Use an external 120VAC coiled relay to bring the generator’s battery voltage
to the AGS run sense port (AGS Terminal Block Port #2) only while the generator is
running. The generator’s battery voltage must be 10 to 40 VDC.
Option 2 - Use a 120VAC to 12VDC step-down transformer (normally used to charge
power equipment batteries) and plug into the generator’s 120VAC output. The step-
down transformer provides 12 VDC output only while the generator is running.
Option 1 - Tap into the positive side of the generator’s hour meter or running light;
ensure the voltage is 10 to 40 VDC only while the generator is running.