© 2010 Magnum Energy, Inc.
3.2 External Settings
The generator run time, temperature, and voltage settings come pre-set
directly from the factory. For the majority of customers, the factory default
settings as shown in Table 3-2 are appropriate. If you need to make changes
to the factory settings, you can do so by rotating the knobs either clockwise or
counterclockwise on the front panel of the AGS Controller; see Figure 3-3.
Q U IE T TIM E
P M /A M
s etting
C LO C K
A M /P M
s etting
S TA R T
V O LTS D C
s etting
S TA R T
TE M P
°F
s etting
R U N TIM E
H O U R S
s etting
RUN TIME HOURS: This setting determines the length of time the generator
will run after the generator has started. The generator starts because the
battery voltage has fallen to the START VOLTS DC setting for at least two
minutes continuously; or, the temperature around the remote switch has
risen to the START TEMP °F setting. The run time can be set from 1 to 5
hours. To change this setting, slowly rotate the knob marked RUN TIME
HOURS clockwise to increase generator run time or counterclockwise to
decrease the generator run time.
Adjustable Settings
Factory Default Values
RUN TIME HOURS
2 (Hours)
START TEMP °F
OFF (disabled)
START VOLTS DC
11 (Volts DC)
CLOCK AM/PM
8A (8 AM)
QUIET TIME PM/AM
OFF (disabled)
INPUT DC VOLTAGE
12 Volts (bottom two pins)
GEN TYPE
QD Mode (all 4 switches off)
EXTERNA
L
SETTI
NGS
IN
TERNA
L
SETTINGS
Table 3-2, ME-AGS-S Default Settings
Figure 3-3, External Settings
3.0 Setup