ME-PT1 Instruction Sheet

Part Number: 64-0025 Rev B 

1

Magnum Energy, Inc.

2211 West Casino Rd.

Everett, WA, USA 98204

www.magnumenergy.com

Introduction

The ME-PT1 (pigtail one-wire) adapter connects to Magnum’s Auto Generator 

Start (ME-AGS) controller to allow the connected generator to start when an 

ex12-volt DC supply is applied. This is useful for applications in which 

there is a need to automatically turn the generator on/off externally, either 

through a manually controlled switch or from an automatically controlled 

switching device.
When +12-volts is supplied to this pigtail wire it causes the AGS controller to 

start and run the connected generator.

Info: The high temperature start feature on the AGS is not available 

when using the ME-PT1. However, the low battery voltage start 

feature is still available.

Installation/Setup – ME-AGS-N (Network Version)

The following pertains to the ME-PT1 when connected to the ME-AGS-N.

Info: Refer to the ME-AGS-N Owner’s Manual (64-0039) for 

installation, setup, and operation of the ME-AGS-N; and to the ME-

RC (64-0003) or ME-ARC owner’s manuals (64-0030) for information 

on selecting/adjusting settings.

Installation

To install the ME-PT1, refer to Figure 1 and the steps below:
1.  Connect the red wire on the ME-PT1 adapter to a +12-volt DC external 

switching device (i.e., switch).

2.  Plug the ME-PT1 adapter into the REMOTE (purple) port on the ME-AGS-N.

Info: The remote temperature sensor that comes with the 

ME-AGS-N (normally plugged into the AGS’s REMOTE port) is not 

used when a ME-PT1 is connected.

Setup

When using the ME-PT1 with the ME-AGS-N, confi gure the ME-RC (or ME-

ARC) to allow the ME-AGS-N to accept the external input from the ME-PT1.
• 

Find the temperature start setting—depending on your remote: ME-RC 

(under AGS/04 Start Temp F menu), or ME-ARC (under SETUP/04E Gen 

Run Temp/Start menu). Then, select the Start=Ext Input setting.

ME-PT1 to ME-AGS-N Operation

The type of external switch (i.e., “momentary” or “maintain”) connected to 

the ME-PT1 adapter determines how long the generator can run.
ME-RC
A. Using a momentary type switch: Pressing the switch causes the generator 

to run for the duration of a full run time cycle (as set in the AGS/03 Run Time 

Hour menu), and then stop.
B. Using a maintain type switch: If the switch is set to ON, the generator 

continues to run until the switch is set to OFF. Once the switch is set to OFF, 

the generator will continue to run for the remaining duration of the current 

run time cycle (as set in the AGS/03 Run Time Hour menu), and then stop. 

Summary of Contents for ME-PT1

Page 1: ...ion To install the ME PT1 refer to Figure 1 and the steps below 1 Connect the red wire on the ME PT1 adapter to a 12 volt DC external switching device i e switch 2 Plug the ME PT1 adapter into the REMOTE purple port on the ME AGS N Info The remote temperature sensor that comes with the ME AGS N normally plugged into the AGS s REMOTE port is not used when a ME PT1 is connected Setup When using the ...

Page 2: ...ion of run time cycle and then stops options PT1 AGS To Network port on Magnum inverter All grounds must be bonded together to ensure the ME PT1 works correctly GEN connection provides 12VDC from Zone Control Box when gen needs to start GEN connection GREEN GND WHITE L2 BLACK L1 ZONE CONTROL BOX 115 VAC IN 9 PIN PLUG TO UPPER UNIT FREEZE ROOM HEAT SHED COOL SHED TO USE WITH LOAD SHED DEVICE REMOVE...

Page 3: ... the phone splitter s ports and then plug the remote switch using its communications cable into the phone splitter s other port 3 Connect the red wire on the ME PT1 adapter to a 12 volt DC external switching device i e switch Temperature Sensor Temperature Sensor cut open Figure 2 Locating Sensor Figure 3 Sensor Cut Open Setup 1 On the ME AGS S turn the START TEMP F adjustment clockwise to any tem...

Page 4: ... current RUN TIME HOURS cycle has been satisfied options GEN connection provides 12VDC from Zone Control Box when gen needs to start GEN connection GREEN GND WHITE L2 BLACK L1 ZONE CONTROL BOX 115VAC IN 9 PIN PLUG TO UPPER UNIT FREEZE ROOM HEAT SHED COOL SHED TO USE WITH LOAD SHED DEVICE REMOVE JUMPER AND CONNECT TO N C CONTATCT ROOM SENSOR FREEZE SENSOR PT1 AGS Phone Splitter 6 conductor ME AGS S...

Reviews: