Mounting Instructions

• Screw backplate to wall or ceiling

NOTE: Optimal mounting is at or below ceiling height and in conditioned environment.
NOTE: Range can vary greatly based on building materials, device positioning, interferance, etc. 
Reference the EnOcean Range Planning Guide prior to installation.

• Attach device to backplate by aligning tabs and twisting / locking into place (see below)

4

Summary of Contents for M9-EBOX

Page 1: ...Gateway BACnet IP Setup Manual M9 EBOX Revision 1 7 071123 1 Seneca Street 29thFloor M55 Buffalo NY 14203...

Page 2: ...ackplate 3 Optional Power Supply upon request 3 Device Overview 3 LED Overview 3 Device Dimensions 3 Port Overview 3 What you need before you begin 3 Mounting Instructions 4 Backplate Mounting 4 Conne...

Page 3: ...evice What you need before you begin PoE Cable 4 screws Screwdriver airConfig Software email support magnumfirst com for download instructions EBOX Device Device Backplate Update Indicator LED Power I...

Page 4: ...w ceiling height and in conditioned environment NOTE Range can vary greatly based on building materials device positioning interferance etc Reference the EnOcean Range Planning Guide prior to installa...

Page 5: ...ransceiver or network card The eBox may be configured without the USB Tranceiver when it can be reached on the network The eBox factory default is DHCP so it will receive and IP Address if a DHCP serv...

Page 6: ...lease find the airConfig panel overview below Drivers for smart devices Smart sensor information Debug output Sensor information Sensors in radio range Queried smart devices Main configuration panel C...

Page 7: ...Ocean USB Transceiver IP query when IP address is unknown does not require USB Transceiver 7 If airConfig is started without the USB Transceiver it will identify EBOXES on the same network automatical...

Page 8: ...ings can be adjusted airConfig requires a network connection to the EBOX for full configuration Control Security Reboot Reboots the EBOX Reset Factory reset that deletes all current configuration as w...

Page 9: ...s for the EBOX 9 1 Actual firmware version of the EBOX and XML file airConfig will prompt if there is a new firmware version available In a case where the EBOX has direct internet access it will also...

Page 10: ...Configuration Process FDR Settings 10 FDR Settings In a case where a BBMD server is present on the network the EBOX can be configured as a foreign device The EBOX is NOT a BBMD server...

Page 11: ...y simply dragging and dropping sensors from the Sensor panel to the Inputs panel You can rename delete and change the BACnet ID of the sensors You will need to send the configuration to the EBOX first...

Page 12: ...d to sensor list Adds output to the sensor list so it can be used as an input for the device it is supposed to control Destination MsgServer Some devices need to be addressed instead of using broadcas...

Page 13: ...utputs either to your local HDD or to the Cloud Change base ID will also change the Base ID of the new EBOX if the destination device is different from the source This will allow the new EBOX to contr...

Page 14: ...into multiple EBOXs range Auto Learn will allow the EBOXs to study the signal strength for the devices After a 5 6 hour period the EBOXs will use that information to assign the devices to the ideal EB...

Page 15: ...vate Rename Data Points Renamed points are shared in the EBOX and will visible in the BACnet system Save EDE Select inputs outputs and EBOX points Since data points are created in the EBOX you will ne...

Page 16: ...device Load Device List Load an EBOX list from a disc Save Device List Save selected EBOXES as a list to a disc Copy Copy the configuration Paste Paste without inputs and outputs Paste All Paste with...