8. Testing the installation
1. All heating foils must be connected
during the test.
2. Measure the overall resistance for the
heating foils and note this in the protocol
under Measured resistance before covering
the floor
3. Calculate the actual power with formula:
Actual power=52900/Measured resistance ;
note in under: Actual power
4. Measure the total length of the heating
film and calculate the Total Rate Power with
the formula: Total Rate Power = total length
x rated in W/m (printed on the heating foil)
Note that under: Total Rated Power
5. Make a sketch or take a photo for
documentation of the installation on the
middle page.
9. Cover the Foil
1. Cover the Foil with age resistant PE foil
with a minimum thickness of 0.1 mm. Film
must overlap 200 mm if it is necessary to use
several sheets to cover the surface (Pic. 15).
2. Install the laminate flooring according to the
manufacturer’s instructions. Please work with
light footwear. Protect the heating foil, cables
and connections with some spare Magnum
Isofoam PS insulation (Pic. 16 and 17).
3. Measure the overall resistance of the
heating foils and note it in the protocol
under: Measured resistance when floor
covering is installed. This protocol should
be filled in completely. In case of a technical
problem, the manufacturer will ask for this
protocol-card. Connect the thermostat
according to the instructions in the
thermostat manual. The thermostat must be
limited to a max. floor temperature of
28
o
C
14
15
16
17