CALIBRATE TENSION THROUGH FIELDBUS
www.maxcessintl.com
DLCA NET-ECAT
MI 850A365 1
Page 65 of 72
9.3
Calibration errors returned
Value
Error description and solution
0x00
Calibration was successful. No Errors found.
0x01
Signal read by the amplifier is too large when maximum tension is applied.
This is caused by maximum tension being too large. Reduce maximum
tension.
0x02
Signal read by the amplifier is too small. Too little of the load cell range is
being used, thus the gain is greater than 32:1. Use more of the load cell range
or set maximum tension higher.
0x03
Roller weight too large. Roller weight exceeds 90% of the load cell rating.
Make roller weight smaller.
0x04
Calibration tension is greater than Maximum tension. Make Maximum tension
larger than Calibration tension.
0x05
Maximum tension exceeds the load cell rating. Lower wrap angle, make roll
weight smaller, get higher rated load cells, or lower maximum tension.
Table 3. Calibration errors