PARAMETERS
www.maxcessintl.com
DLCA NET-ECAT
MI 850A365 1
Page 35 of 72
7.0
Parameters
This section describes the parameters available in the DLCA NET-ECAT.
7.1
Filtering
The tension display and the analog outputs have a separate low pass filter. The
communication tension values can use either the tension display filter or have no filtering.
The tension display filter response can be set from 500 Hz to 0.01 Hz.
The analog output filter response can be set from 100 Hz to 0.01Hz.
The filters are a second order low pass filter for frequencies from 0.01 Hz to 124.99 Hz.
Above 125 Hz, an average of samples is used for the filter, as defined in this table.
Frequency (Hz)
averages used
125.00 to 166.66
Four samples
166.67 to 249.99
Three samples
250.00 to 499.99
Two samples
500.00
There is no filter; current sample data is used
Parameter Description
Units
Default
Range
Fd.1
Tension 1 display filter frequency
0.01 Hz
3.00
{00.01,
500.00}
Fd.2
Tension 2 display filter frequency
0.01 Hz
3.00
{00.01,
500.00}
FO.1
Output 1 filter frequency
0.01 Hz
40.00
{00.01,
100.00}
FO.2
Output 2 filter frequency
0.01 Hz
40.00
{00.01,
100.00}
FO.3
Output 3 filter frequency
0.01 Hz
40.00
{00.01,
100.00}
FO.4
Meter Output filter frequency
0.01 Hz
40.00
{00.01,
100.00}
P.09
Filter Communication Tension
0
{0, 1}
0 = no filtering on communication
tension values.
1 = use display filter frequency on
communication tension
values.