5. Technical Data
Housing dimensions with connectors
and feet (W x H x D)
1070 x 463 x 400 mm
Construction
Sandwich construction with
20 mm thermal insulation
Material/colour
Sheet steel, galvanised
Duct connection
DN 125 mm
Condensation connection
½" hose
Protection class
1
Degree of protection
IP 00
External filter/Exhaust air filter
Dust filter,
filter class G4
Permitted ambient temperature
+10 ... +40 °C
Permitted outside air temperature
-15 ... +60 °C
Weight
approx. 53 kg
Housing emission at 100 m³/h
35 dB(A)
Electrical data
Supply voltage / frequency
230 V~, 50/60 Hz
Power consumption, free outlet
70 m³/h
11 W
100 m³/h
17 W
135 m³/h
27 W
Fan levels (Base settings = bold)
Step 3 (intensive ventilation, party operation):
165 m³/h, 150 m³/h,
135 m³/h, 120 m³/h
Step 2 (normal ventilation, daytime operation):
135 m³/h, 120 m³/h,
100 m³/h, 85 m³/h
Step 1 (basic ventilation, nighttime operation):
105 m³/h, 95 m³/h,
85 m³/h, 70 m³/h
Volumetric flow adjustment on the
exhaust air side
-10 ... +10 %
Base factory setting
0 %