background image

 

 

 

 

11 

 Remove terminal box cover [7] from EAT 6 

G/1 unit [1]. 

 Cut through desired cable lead-throughs at 

knockout points on underside of EAT 6 G/1 

housing.  

 

CAUTION 

Unit will be damaged by water 

ingress or moisture. 

 Only lead cables into EAT 6 

G/1 housing from underneath. 

If this is not done, the degree 

of protection cannot be 

guaranteed. 

 Hang EAT 6 G/1 unit on central screw and 

secure in the bottom right and left with  

2 locking bolts. Suitable mounting material 

is to be provided by the customer. 

 Guide all connecting cables into the 

housing. 

 Remove cover from temperature sensor 

[13]. 

 Cut through desired cable lead-through at 

one knockout point on side  

of temperature sensor housing. 

 Fit cable grommet on housing. 

 Fit temperature sensor housing on wall. For 

spacing, refer to rear of housing. Suitable 

mounting material is to be provided by the 

customer. 

 Feed cable into the housing. 

 

8. Electrical connection 

 

 

CAUTION 

Risk of damage to unit in the 

event of short-circuits! 

 Cut off and insulate cable 

cores that are not required. 

 

  

Information 

 

● EAT 6 G/1 unit is fitted with a 0...10 V 

output for optional EALT 6 power unit 

(for permitted maximum loading = 12 A). 

● The output voltage at EALT 6 (+/- terminal) 

is proportional to the controlled 0...10 V 

voltage. 

 

Connecting temperature controller 

 Strip cables. 

 Connect power cable and control cables as 

shown in wiring diagram on page 7. 

 Fit cover on temperature sensor [13]. 

Ensure that the sealing in the cover is 

inserted correctly and is sealed all the way 

around. 

 Check position of jumper [12] in EAT 6 G/1 

terminal box and move if desired: 

Limit value switch, On.

 

Fan switches off when temperature 

falls below setpoint temperature by 

at least 3 °C and switches back on 

when setpoint temperature is 

exceeded. 

Limit value switch, Off.

 

Fan runs at minimum speed when 

temperature falls below setpoint 

temperature by at least 3 °C. 

 Fit terminal box cover [7] on EAT 6 G/1  

unit [1]. 

 Switch the mains fuse on. 

 Run function test. 

 

9. Commissioning – temperature-

controlled operation 

 Move operating mode switch [2] into 

“Automatic” position. 

● Unit switches on. 

 Use potentiometer [5] to set “XP” speed 

range: 

– All the way to the left, approx. 2 K 

– All the way to the right, approx. 10 K 

 Use rotary knob [7] to select setpoint 

temperature. Setting range      5...35 °C. 

 Use potentiometer [6] to select maximum 

fan speed.  

 Use potentiometer [4] to select minimum 

fan speed. 

 

Summary of Contents for EAT 6 G/1

Page 1: ...itung Temperaturregelsystem Installation and operating instructions for temperature control system Notice de montage et mode d emploi Syst me de r gulation de temp rature EAT 6 G 1 www maico ventilato...

Page 2: ...2...

Page 3: ...lektrischer Anschluss 6 9 Inbetriebnahme Regelbetrieb 6 10 Inbetriebnahme Dauerbetrieb 7 11 Ger t ausschalten 7 12 Wartung 7 13 Reinigung 7 14 St rungsbehebung 7 15 Demontage 7 16 Umweltgerechte Entso...

Page 4: ...n gegen Wiedereinschalten sichern und ein Warnschild sichtbar anbringen Ger t nur komplett montiert betreiben Ein besch dig tes Ger t nicht in Betrieb nehmen Ein Betrieb ist nur mit Original Komponent...

Page 5: ...empe ratur 5 K ber der Solltemperatur erreicht F llt die Raumtemperatur min 3 C unter die Solltemperatur wird die Ventilator drehzahl entweder per Grenzwertabschaltung reguliert Ventilator schaltet au...

Page 6: ...nem 0 10 V Ausgang f r optionales Leistungsteil EALT 6 ausger stet f r zul ssige Maximalbelastung 12 A Die Ausgangsspannung zum EALT 6 Klemme ist proportional zur geregelten Spannung 0 10 V Temperatur...

Page 7: ...nung Netzsicherung ausschalten St rung Ma nahme Bei Kurzschluss oder Unterbrechung der Steuerungsleitung zum Temperaturf hler erfolgt Betrieb des Ventilators mit Mindestdrehzahl Rote Kontrollleuchte 9...

Page 8: ...on 11 9 Commissioning temperature controlled operation 11 10 Commissioning continuous operation 12 11 Switching off unit 12 12 Maintenance 12 13 Cleaning 12 14 Fault rectification 12 15 Dismantling 12...

Page 9: ...ompletely installed Do not commission a damaged unit The unit may only be operated with original components Changes and modifications are not permitted and release the manufacturer from any guarantee...

Page 10: ...m temperature 5 K above the setpoint temperature If the room temperature falls at least 3 C below the setpoint temperature the fan speed is either controlled using limit value switch off The fan switc...

Page 11: ...V output for optional EALT 6 power unit for permitted maximum loading 12 A The output voltage at EALT 6 terminal is proportional to the controlled 0 10 V voltage Connecting temperature controller Stri...

Page 12: ...short circuit or if cable to temperature sensor is interrupted the fan will run at minimum speed Red indicator light 9 switches on Call on the services of a qualified electrician Micro fuse has tripp...

Page 13: ...temp rature Sommaire 1 Qualification de l installateur sp cialis 13 2 Utilisation conforme 14 3 Consignes de s curit et avertissements 14 4 Informations produit 15 5 Conditions environnementales et li...

Page 14: ...la chaleur ou par formation d tincelles et de provoquer un incendie Des gaz et poussi res explosifs risquent de s enflammer et de provoquer une grave explosion ou un incendie Ne jamais utiliser l app...

Page 15: ...des de fonctionnement avec interrupteur 2 Mode automatique fonctionnement r gul par thermostat la temp rature ambiante change gr ce l alimentation en air ext rieur par ventilateur jusqu ce que la temp...

Page 16: ...e pas dans un coin position de montage de la sonde de temp rature admissible seulement vers le bas Effectuer le c blage pour des types admis sibles voir chapitre 4 entre l appareil EAT 6 G 1 et la son...

Page 17: ...et la modifier si vous le souhaitez Coupure valeur limite Marche Le ventilateur s arr te si la temp rature est inf rieure d au moins 3 C la temp rature de consigne et red marre si cette temp rature es...

Page 18: ...c ble de commande de la sonde de temp rature le ventilateur fonctionne vitesse de rotation minimale Le t moin lumineux rouge 9 s allume Faire appel un lectricien qualifi Le fusible pour courant faible...

Page 19: ...19...

Page 20: ...ingen Germany Service 49 7720 6940 info maico de 03 21_Es 0185 1112 0002_RLF 7_03 21_DSW EAT6 G 1 Temperaturregler Temperature controller R gulateur de temp rature EALT6 Leistungsteil Power unit l men...

Reviews: