6 Technical data

16

• Overrun time can be adjusted from 3 to 25

minutes (factory setting 6 minutes).

• On/off with light switch or separate switch.

• Not speed-controllable.

• Required mains cable 5 x 1.5 mm².

5.3 ECA piano H

• Small room fans for extracting air from rooms.

• Model with humidity control (automatic humidity

function) and adjustable overrun time.

ECA piano H

 with fixed internal grille.

• Barrier-free product as the fan switches itself on

and off automatically.

• Switch-on humidity can be adjusted from 50 %

r.h. to 90 % r.h. (factory setting 70% r.h.).

• With an additional switch, it is possible to switch

manually. The fan then runs on for the set over-
run time.

• Overrun time can be adjusted from 0.5 to 18

minutes (factory setting 12 minutes).

• Not speed-controllable.

• Required mains cable 3 x 1.5 mm². When using

an optional switch, provide a 5 x 1.5 mm² mains
cable.

• Automatic humidity function with priority.

Humidity function depending on connection
variant 1 or 2.

Connection variant 1

Fan switches on automatically when the relat-
ive room humidity in the area of the fan ex-
ceeds the preset switching point. Switching
off takes place after the humidity has fallen
below the switching point and the set overrun
time has elapsed. With additional switch
“S1”,the fan can be switched off manually.

Connection variant 2

Fan is turned on via the automatic humidity
function, as in connection variant 1, or manu-
ally (light switch). 

Note:

 With a relative room

humidity over the switching point, the fan can
no longer be switched off, not even with the
light switch. 
The fan switches off when the room humidity
in the area of the fan is under the switching
point and the overrun time has elapsed.

6 Technical data

6.1 Ambient conditions

• Permissible maximum temperature of air me-

dium + 40 °C.

• Resistance to interference according to EN

55014-2 depending on pulse shape and energy
component 1000 to 4000 V. If operating with
fluorescent tubes, extra interference suppres-
sion measures are needed (L or C components
or RC modules, protection diodes, varistors) be-
cause these values may be exceeded.

• Recommendation: When operating on switches

with a glow lamp, wire an X2 capacitor (220
nF/250 V) to zero. The capacitor is to be
provided by the customer.

• Storage: Store unit exclusively in a dry location

(-20 to +50 °C).

6.2 Technical data table

Rated voltage

230 V AC

Power frequency

50/60 Hz

Sound pressure level

26 dB(A)

Degree of protection

IP X4

Weight

0.5 kg

For more technical data → rating plate.

For characteristic curves → 

www.maico-ventil-

atoren.com

.

7 Preparation for installation

7.1 Wall

Use mounting material suitable for base and of
sufficient dimensions. Ensure sufficient supply air.

 The prescribed minimum distances to the

wall and the ceiling shown in the figure must
be observed.

1. Make sure the housing has a level base.

2. Fit wall breakthrough or drill core hole. Min-

imum diameter, 105 mm.

ð

Recommendation: Fit WH 100 wall sleeve.
Fit wall breakthrough with minimum dia-
meter 115 mm.

Summary of Contents for ECA piano

Page 1: ...und Betriebsanleitung Installation and operating instructions Notice de montage et mode d emploi ECA piano STANDARD ECA piano TC ECA piano H Kleinraumventilatoren Small room fans A rateurs pour petite...

Page 2: ...Inhaltsverzeichnis Deutsch 3 English 12 Fran ais 21...

Page 3: ...r te bersicht 1 Geh use mit Motor 2 Platinentr ger 2 1 Klemmleiste ECA piano STANDARD 2 2 Timerplatine ECA piano TC 2 3 Feuchteplatine ECA piano H 3 Motordeckel 4 Abdeckung 5 Dichtring 6 Klappe 7 Fl g...

Page 4: ...H 7 6 Technische Daten 7 6 1 Umgebungsbedingungen 7 6 2 Technische Datentabelle 7 7 Montagevorbereitungen 7 7 1 Wand 7 7 2 Decke 8 7 3 Rohr 8 7 4 Geh use 8 7 5 Vorbereitungen f r den Betrieb mit Drehz...

Page 5: ...Ger t darf in folgenden Situationen auf kei nen Fall eingesetzt werden GEFAHR Entz ndungs Brandgefahr durch brennbare Materialien Fl ssigkeiten oder Gase in der N he des Ger ts In der N he des Ger ts...

Page 6: ...r eine ausreichende Zuluftnachstr mung sorgen GEFAHR Gefahr durch Stromschlag bei Betrieb mit nicht komplett montiertem oder besch digtem Ventilator Vor dem Abnehmen des Elektronikabdeckung al le Vers...

Page 7: ...olgt nach Unter schreiten des Schaltpunktes und anschlie endem Ablauf einer einstellbaren Nachlauf zeit Mit zus tzlichem Schalter S1 l sst sich der Ventilator manuell ausschalten Anschlussvariante 2 V...

Page 8: ...ermisch isolie ren Kondenswasserableitung oder Kondensat sammler in der Steigleitung einplanen 7 3 Rohr 1 Kanten der Rohrinnenseite entgraten 2 Montagevorbereitungen wie in Kapitel Wand beschrieben vo...

Page 9: ...Nachlauf zeit einstellen ab Werk ca 6 Minuten 9 00 Uhr ECA piano H Mit Potentiometer P1 die Nachlauf zeit einstellen ab Werk ca 12 Minuten 12 00 Uhr ECA piano H Mit Potentiometer P2 den Feuchte schal...

Page 10: ...trofachkraft hinzu ziehen Reparaturen sind nur durch Elektro fachkr fte zul ssig St rung Ursache Ma nahmen Ventilator schaltet nicht ein Keine Netzspannung Pr fen ob die Netzsiche rung ausgefallen ist...

Page 11: ...n 3 Motordeckel abnehmen 15 Umweltgerechte Entsorgung Das Ger t und auch die Verpackung enthalten wiederverwertbare Stoffe die nicht in den Rest m ll gelangen d rfen Entsorgen Sie die Verpa ckungsmate...

Page 12: ...1 Housing with motor 2 Circuit board holder 2 1 Terminal block ECA piano STANDARD 2 2 Timer circuit board ECA piano TC 2 3 Humidity circuit board ECA piano H 3 Motor cover 4 Cover 5 Gasket 6 Shutter...

Page 13: ...ta 16 6 1 Ambient conditions 16 6 2 Technical data table 16 7 Preparation for installation 16 7 1 Wall 16 7 2 Ceiling 17 7 3 Duct 17 7 4 Housing 17 7 5 Preparations for operation with speed controller...

Page 14: ...in the following situ ations under any circumstances DANGER Risk of combustion fire from flammable materials liquids or gases in the vicinity of the unit Do not place any flammable materials liquids o...

Page 15: ...on and position a visible warning sign Only operate the fan when it is completely in stalled Do not commission a damaged unit DANGER Danger if the relevant regula tions for electrical installations a...

Page 16: ...nt 1 or manu ally light switch Note With a relative room humidity over the switching point the fan can no longer be switched off not even with the light switch The fan switches off when the room humid...

Page 17: ...roperly posi tioned 2 ECA piano STANDARD ECA piano TC If necessary use auxiliary materials e g foam strip for fixing in wall or duct When doing so maintain a minimum distance of 20 mm to the end of th...

Page 18: ...umidity switching point with potentiometer P2 Stop all the way to the left approx 50 r h 12 00 o clock see figure factory setting approx 70 Stop all the way to the right ap prox 90 r h 8 3 Final mount...

Page 19: ...ed electrician Call on the services of a qualified electrician any time there is a fault Repairs should only be carried out by a qualified electrician Fault Cause measures Fan does not switch on No ma...

Page 20: ...l The unit and the packaging contain parts that can be recycled and should not end up in the do mestic waste Dispose of the packaging material and the unit in an environmentally friendly way in compli...

Page 21: ...pareil 1 Bo tier avec moteur 2 Porte platine 2 1 R glette de bornier ECA piano STAN DARD 2 2 Platine minuterie ECA piano TC 2 3 Platine humidit ECA piano H 3 Couvercle du moteur 4 Cache de protection...

Page 22: ...26 6 2 Tableau de donn es techniques 26 7 Pr paratifs de montage 26 7 1 Mur 26 7 2 Plafond 26 7 3 Gaine ronde 27 7 4 Bo tier 27 7 5 Pr paration pour l utilisation avec r gulateur de vitesse 27 8 Monta...

Page 23: ...e rectangulaire ou ronde branchement lectrique encastr Cet appareil est exclusivement r serv l usage domestique et similaires 4 Consignes de s curit 4 1 Consignes de s curit g n rales Ne jamais utilis...

Page 24: ...T Risque de blessure et pour la sant en cas de modifications ou de transformations ou encore en cas d utilisation de composants non autoris s Le fonctionnement n est autoris qu avec des composants d o...

Page 25: ...pour petite pi ce destin l vacua tion d air des locaux Version standard ECA piano avec grille int rieure fixe Marche Arr t par interrupteur d clairage ou interrupteur s par vitesse variable C ble d al...

Page 26: ...andation en cas d utilisation des inter rupteurs lumineux connecter un condensateur X2 220 nF 250 V au fil neutre Le condensa teur est fournir par le client Stockage Stocker l appareil uniquement dans...

Page 27: ...0 mm par rapport l extr mit du raccord Ne pas recouvrir l at tache des volets fl che ECA piano H positionner le ruban en mousse comme d crit pr c demment Ceci est important afin que l appareil n attir...

Page 28: ...des volets 2 Activer le fusible secteur 3 Effectuer un test de fonctionnement 9 Utilisation ECA piano STANDARD Marche Arr t avec interrupteur d clairage ou in terrupteur s par les deux fournir par le...

Page 29: ...alifi s Dysfonctionnement Cause mesures Le ventilateur ne se met pas en marche Pas de tension du sec teur Contr ler si le fu sible secteur fonctionne correctement Le cas ch ant l activer Le ventilateu...

Page 30: ...ent r serv des lectriciens qualifi s 14 1 Enlever le cache de protection les crochets d arr t le couvercle du moteur 3 Couvercle du moteur 1 Retirer d abord le cache de protection dans le tiers inf ri...

Page 31: ...brik GmbH Traduc tion du mode d emploi d origine en langue alle mande Sous r serve de fautes d impression d erreurs et de modifications techniques Les marques marques commerciales et marques d pos es...

Page 32: ...Maico Elektroapparate Fabrik GmbH Steinbeisstr 20 78056 Villingen Schwenningen Deutschland Service 49 7720 6940 info maico de 0185 1111 0005_RLF 8_04 21_DSW AS...

Reviews: