10 Maintenance

19

Variant 1: Fan switches on automatically when
the relative room humidity in the area of the fan
exceeds the preset switching point. Switching off
takes place after the humidity has fallen below the
switching point and the set overrun time has
elapsed. With additional switch S1, the fan can be
taken out of operation.
Variant 2: Fan switches on automatically via hu-
midity control (as in variant 1) 

or

 manually via

light switch. With a relative room humidity over
the switching point, the fan can no longer be
switched off, not even with the light switch. The
fan switches off when the room humidity in the
area of the fan is under the switching point and
the overrun time has elapsed.

10 Maintenance

The unit is maintenance-free.

11 Cleaning

 Clean fan regularly, especially after it has

not been used for a long time.

NOTICE Risk of damage to unit if incorrect
cleaning agent is used.

Only clean the cover(s) using water.
Do not use aggressive cleaning agents.

1. Only use a dry cloth to clean the internal parts

of the fan.

2. If the cover is very dirty, carefully remove it

and clean with water.

3. Fit cover.

4. Run function test.

12 Fault rectification

 Fault finding only by qualified electrician.

Call on the services of a qualified electrician
any time there is a fault. Repairs should only
be carried out by a qualified electrician.

Fault

Cause, measures

Fan does not switch
on.

No mains voltage.

Check whether the mains
fuse has failed. Switch on
if necessary.

Fan does not switch
off.

Overrun time (max. 25
min.).

 Wait for overrun

time and reduce if neces-
sary.

Motor’s thermal over-
load protection
switches the fan off.

Motor too hot.

 Wait until

the motor has cooled
down. Cool-down time
can be up to 10 minutes.
Unit switches back on
automatically after cool-
ing down.

Fan does not switch
off or fan switches on
when not wanted.

A high-impedance
voltage is present at
terminal L1 due to a
glow lamp in the con-
trol switch, cables laid
in parallel (induction)
or transformers or
other electrical com-
ponents.

 Recommenda-

tion: Wire X2 capacitor
(220 nF/ 250 V) to zero.

13 Spare parts

 Spare parts may only be sourced from and

fitted by a specialist installer.

Designation

Article no.

Covers

ABD ECA piano 1

E059.1125.9000

ABD ECA piano 2

E059.1125.9100

Printed circuit boards

PL ABDE ECA piano
TC

E101.1403.0001

PL ABDE ECA piano H E101.1402.0002

Capacitor

KS RCA ER

E157.0116.0000

In case of questions, please contact:

Maico Elektroapparate-Fabrik GmbH
Steinbeisstraße 20
78056 Villingen-Schwenningen, Deutschland
Tel. +49 7720 694 445
Fax +49 7720 694 175
E-mail: 

ersatzteilservice@maico.de

Summary of Contents for ECA piano

Page 1: ...und Betriebsanleitung Installation and operating instructions Notice de montage et mode d emploi ECA piano STANDARD ECA piano TC ECA piano H Kleinraumventilatoren Small room fans A rateurs pour petite...

Page 2: ...Inhaltsverzeichnis Deutsch 3 English 12 Fran ais 21...

Page 3: ...r te bersicht 1 Geh use mit Motor 2 Platinentr ger 2 1 Klemmleiste ECA piano STANDARD 2 2 Timerplatine ECA piano TC 2 3 Feuchteplatine ECA piano H 3 Motordeckel 4 Abdeckung 5 Dichtring 6 Klappe 7 Fl g...

Page 4: ...H 7 6 Technische Daten 7 6 1 Umgebungsbedingungen 7 6 2 Technische Datentabelle 7 7 Montagevorbereitungen 7 7 1 Wand 7 7 2 Decke 8 7 3 Rohr 8 7 4 Geh use 8 7 5 Vorbereitungen f r den Betrieb mit Drehz...

Page 5: ...Ger t darf in folgenden Situationen auf kei nen Fall eingesetzt werden GEFAHR Entz ndungs Brandgefahr durch brennbare Materialien Fl ssigkeiten oder Gase in der N he des Ger ts In der N he des Ger ts...

Page 6: ...r eine ausreichende Zuluftnachstr mung sorgen GEFAHR Gefahr durch Stromschlag bei Betrieb mit nicht komplett montiertem oder besch digtem Ventilator Vor dem Abnehmen des Elektronikabdeckung al le Vers...

Page 7: ...olgt nach Unter schreiten des Schaltpunktes und anschlie endem Ablauf einer einstellbaren Nachlauf zeit Mit zus tzlichem Schalter S1 l sst sich der Ventilator manuell ausschalten Anschlussvariante 2 V...

Page 8: ...ermisch isolie ren Kondenswasserableitung oder Kondensat sammler in der Steigleitung einplanen 7 3 Rohr 1 Kanten der Rohrinnenseite entgraten 2 Montagevorbereitungen wie in Kapitel Wand beschrieben vo...

Page 9: ...Nachlauf zeit einstellen ab Werk ca 6 Minuten 9 00 Uhr ECA piano H Mit Potentiometer P1 die Nachlauf zeit einstellen ab Werk ca 12 Minuten 12 00 Uhr ECA piano H Mit Potentiometer P2 den Feuchte schal...

Page 10: ...trofachkraft hinzu ziehen Reparaturen sind nur durch Elektro fachkr fte zul ssig St rung Ursache Ma nahmen Ventilator schaltet nicht ein Keine Netzspannung Pr fen ob die Netzsiche rung ausgefallen ist...

Page 11: ...n 3 Motordeckel abnehmen 15 Umweltgerechte Entsorgung Das Ger t und auch die Verpackung enthalten wiederverwertbare Stoffe die nicht in den Rest m ll gelangen d rfen Entsorgen Sie die Verpa ckungsmate...

Page 12: ...1 Housing with motor 2 Circuit board holder 2 1 Terminal block ECA piano STANDARD 2 2 Timer circuit board ECA piano TC 2 3 Humidity circuit board ECA piano H 3 Motor cover 4 Cover 5 Gasket 6 Shutter...

Page 13: ...ta 16 6 1 Ambient conditions 16 6 2 Technical data table 16 7 Preparation for installation 16 7 1 Wall 16 7 2 Ceiling 17 7 3 Duct 17 7 4 Housing 17 7 5 Preparations for operation with speed controller...

Page 14: ...in the following situ ations under any circumstances DANGER Risk of combustion fire from flammable materials liquids or gases in the vicinity of the unit Do not place any flammable materials liquids o...

Page 15: ...on and position a visible warning sign Only operate the fan when it is completely in stalled Do not commission a damaged unit DANGER Danger if the relevant regula tions for electrical installations a...

Page 16: ...nt 1 or manu ally light switch Note With a relative room humidity over the switching point the fan can no longer be switched off not even with the light switch The fan switches off when the room humid...

Page 17: ...roperly posi tioned 2 ECA piano STANDARD ECA piano TC If necessary use auxiliary materials e g foam strip for fixing in wall or duct When doing so maintain a minimum distance of 20 mm to the end of th...

Page 18: ...umidity switching point with potentiometer P2 Stop all the way to the left approx 50 r h 12 00 o clock see figure factory setting approx 70 Stop all the way to the right ap prox 90 r h 8 3 Final mount...

Page 19: ...ed electrician Call on the services of a qualified electrician any time there is a fault Repairs should only be carried out by a qualified electrician Fault Cause measures Fan does not switch on No ma...

Page 20: ...l The unit and the packaging contain parts that can be recycled and should not end up in the do mestic waste Dispose of the packaging material and the unit in an environmentally friendly way in compli...

Page 21: ...pareil 1 Bo tier avec moteur 2 Porte platine 2 1 R glette de bornier ECA piano STAN DARD 2 2 Platine minuterie ECA piano TC 2 3 Platine humidit ECA piano H 3 Couvercle du moteur 4 Cache de protection...

Page 22: ...26 6 2 Tableau de donn es techniques 26 7 Pr paratifs de montage 26 7 1 Mur 26 7 2 Plafond 26 7 3 Gaine ronde 27 7 4 Bo tier 27 7 5 Pr paration pour l utilisation avec r gulateur de vitesse 27 8 Monta...

Page 23: ...e rectangulaire ou ronde branchement lectrique encastr Cet appareil est exclusivement r serv l usage domestique et similaires 4 Consignes de s curit 4 1 Consignes de s curit g n rales Ne jamais utilis...

Page 24: ...T Risque de blessure et pour la sant en cas de modifications ou de transformations ou encore en cas d utilisation de composants non autoris s Le fonctionnement n est autoris qu avec des composants d o...

Page 25: ...pour petite pi ce destin l vacua tion d air des locaux Version standard ECA piano avec grille int rieure fixe Marche Arr t par interrupteur d clairage ou interrupteur s par vitesse variable C ble d al...

Page 26: ...andation en cas d utilisation des inter rupteurs lumineux connecter un condensateur X2 220 nF 250 V au fil neutre Le condensa teur est fournir par le client Stockage Stocker l appareil uniquement dans...

Page 27: ...0 mm par rapport l extr mit du raccord Ne pas recouvrir l at tache des volets fl che ECA piano H positionner le ruban en mousse comme d crit pr c demment Ceci est important afin que l appareil n attir...

Page 28: ...des volets 2 Activer le fusible secteur 3 Effectuer un test de fonctionnement 9 Utilisation ECA piano STANDARD Marche Arr t avec interrupteur d clairage ou in terrupteur s par les deux fournir par le...

Page 29: ...alifi s Dysfonctionnement Cause mesures Le ventilateur ne se met pas en marche Pas de tension du sec teur Contr ler si le fu sible secteur fonctionne correctement Le cas ch ant l activer Le ventilateu...

Page 30: ...ent r serv des lectriciens qualifi s 14 1 Enlever le cache de protection les crochets d arr t le couvercle du moteur 3 Couvercle du moteur 1 Retirer d abord le cache de protection dans le tiers inf ri...

Page 31: ...brik GmbH Traduc tion du mode d emploi d origine en langue alle mande Sous r serve de fautes d impression d erreurs et de modifications techniques Les marques marques commerciales et marques d pos es...

Page 32: ...Maico Elektroapparate Fabrik GmbH Steinbeisstr 20 78056 Villingen Schwenningen Deutschland Service 49 7720 6940 info maico de 0185 1111 0005_RLF 8_04 21_DSW AS...

Reviews: