9

3.2 Product description 

EDR.. duct fans are diagonal fans with inlet 
flange, stator and a diffuser at the air exit. 
This design makes possible even flows and 
quiet operation. 

3.2.1 EDR 25, EDR 40 

  230 V duct fan. For ventilation or air 

extraction, depending on installation 
position. 

 On/off with separate switch. The fan unit 

switches on/off immediately when the 
switch is operated. 

  Speed control available when transformer 

is used. Speed control using phase angles 
is not permitted. 

  Direction of rotation cannot be changed  

(no reverse operation). 

  In the event of thermal overload, an 

integrated motor overload protection 
switches the unit off. 

3.2.2 EDR 31, EDR 35, EDR 45, EDR 50 

  230 V duct fan. For ventilation or air 

extraction, depending on installation 
position. 

 On/off with separate switch.. The fan unit 

switches on/off immediately when the 
switch is operated. 

  Speed control available when transformer 

is used. Speed control using phase angles 
is not permitted.  

  Direction of rotation cannot be changed  

(no reverse operation). 

  Fan motor with thermal contacts on 

terminal connections. These must be 
switched on a suitable triggering device, 
e.g. the Maico motor protection switch  
MVE 10. The triggering device may not 
switch itself back on automatically after 
triggering. 

3.2.3 EDR 56, EDR 63, EDR 71 

  400 V duct fan. For ventilation or air 

extraction, depending on installation 
position. 

  On/off with separate switch. The fan unit 

switches on/off immediately when the 
switch is operated. 

 Speed controllable with frequency 

converter. Not suitable for operation with 
transformers. On/Off only if there is no 
frequency converter. 

  Direction of rotation cannot be changed  

(no reverse operation). 

  Fan motor interconnected with thermal 

contacts. Motor monitoring using frequency 
converter. 

 
 

4.

 Technical data  

See rating plate, valid catalogue or Internet. 

  Rated voltage, depending on unit type:  

230 V or 400 V 3+N+PE 

 Power frequency: 50 Hz 

 Weight: 

EDR 25:   5 kg 

EDR 50: 23 kg 

EDR 31: 16 kg 

EDR 56: 29 kg 

EDR 35: 18 kg 

EDR 63: 39 kg 

EDR 40: 16 kg 

EDR 71: 48 kg 

EDR 45: 19 kg 

  Degree of protection: IP X4, when installed 

in ducts with at least 1 m of duct on the 
inlet and outlet sides.  

  Maximum permitted temperature of the air 

medium: + 50 °C 

 

GB

Summary of Contents for EDR 25

Page 1: ...Duct fans Ventilateurs pour gaines ronde EDR 25 EDR 56 EDR 31 EDR 63 EDR 35 EDR 71 EDR 40 EDR 45 EDR 50 Montage und Betriebsanleitung Mounting and Operating instructions Instructions de montage et Mod...

Page 2: ...g kann zu Sachsch den f hren 2 2 Sonstige Symbole INFO Symbol Mit diesem Symbol versehene Text passagen geben Ihnen wichtige Informationen und Tipps Aufz hlungssymbol Liste mit wichtigen Informatio ne...

Page 3: ...in Reversierbetrieb Ventilatormotor mit Thermokontakten auf Klemmen gef hrt Diese m ssen auf ein passendes Ausl seger t geschaltet werden z B Maico Motorvollschutz schalter MVE 10 Das Ausl seger t dar...

Page 4: ...von Maschinen r umen Ausstellungsr umen Werkst tten Fabrikationsst tten Industriehallen etc Auch zur Maschinen oder Arbeitsplatz absaugung geeignet Zur Aufputzmontage an Wand Decke oder Konsole F r de...

Page 5: ...iger Umgebung Luftfilter in die Rohrleitung einbauen z B Maico TFE 7 Montage 7 1 Einbau ACHTUNG Funktionsst rung und Ger te besch digung durch streifendes Fl gelrad 1 bei fehlerhaftem Einbau Rohrventi...

Page 6: ...sig Ohne Frequenzumrichter nur Ein Aus Vorgehensweise Klemmenkastendeckel entfernen und lose Komponenten herausnehmen Klemmenkasten an einer der Sollbruch stellen durchsto en Kabelverschraubung 5 anbr...

Page 7: ...e Abk hlzeit kann bis zu 30 Minuten betragen Ger t erst dann wieder einschalten Besteht die St rung weiterhin Elektrofachkraft hinzuziehen Ablagerungen am Fl gelrad und im Geh use durch staubhaltige L...

Page 8: ...ols INFO symbol Text passages marked with this symbol contain important information and tips List symbol List with important information about the corres ponding subject Action symbol List of work to...

Page 9: ...o reverse operation Fan motor with thermal contacts on terminal connections These must be switched on a suitable triggering device e g the Maico motor protection switch MVE 10 The triggering device ma...

Page 10: ...ille 5 2 Intended use For the ventilation or the extraction of air from machine rooms showrooms workshops manufacturing areas industrial buildings etc Also suitable for machine or workplace air extrac...

Page 11: ...operating the unit in a dusty environment 7 Assembly 7 1 Installation NOTICE Faulty operation and unit damage caused by a rubbing impeller 1 with incorrect installation Do not twist the duct fan durin...

Page 12: ...formers is not permitted On Off only if there is no frequency converter Procedure Remove the terminal box cover and take out loose components Make a hole in the terminal box at one of the breakout po...

Page 13: ...nit back on once cool If the fault persists call on the services of a trained electrician Deposits on the impeller and in the housing caused by dust in the air Call on the services of a trained specia...

Page 14: ...d avertissement peut entra ner des dommages mat riels 2 2 Autres symboles Symbole INFO Les passages accompagn s de ce symbole fournissent des informations et conseils importants Symbole d num ration L...

Page 15: ...ion ne peut tre invers pas de fonctionnement r versible Moteur du ventilateur thermocontacts raccord s aux bornes Ces derni res doivent tre connect es sur un d clencheur adapt comme par ex le disjonct...

Page 16: ...s chutes ou l aspiration de corps trangers En cas d aspiration ou de soufflage l air libre ne jamais faire fonctionner sans grille de protection monter une grille de protection Maico SG par ex 5 2 Uti...

Page 17: ...nction du type de ventilateur Utiliser uniquement des tuyaux agraf s adapt s au diam tre nominal Pour viter la transmission de vibrations au syst me de canalisation relier les conduits au ventilateur...

Page 18: ...s parties correspondantes Le conduit de raccordement qui s pare le secteur du bornier doit tre bien fix La r gulation de vitesse des appareils EDR 25 EDR 31 EDR 35 EDR 40 EDR 45 et EDR 50 s effectue a...

Page 19: ...lectrocution Couper le fusible secteur avant les r parations Dysfonction nement Mesure Arr t de l appareil V rifier que le fusible secteur est enclench La protection thermique contre les surcharges d...

Page 20: ...beisstr 20 78056 Villingen Schwenningen Deutschland Service Hotline SAV 49 1805 694 110 info maico de M A I N A U X C TP L N TW TW U2 V2 W2 U1 V1 W1 g n y e b k 5 b k 4 b k 1 b k 2 b k 3 L1 L2 L3 TWTW...

Reviews: