7. Product information
10
7.4.6 ER-UP controls (circuit board types)
ER-UP fans are available in various models
and with various unit properties. These
depend on the control/circuit board type used
in the fan insert [11].
The circuit variants and functions
suited to the circuit board type are
described in chapter 22. Tolerance of
all time details max. + 20 %.
●
Standard model
●
VZ model
: with start delay and overrun
time.
●
VZ 15 model
with start delay and overrun
time.
●
VZC model
with adjustable start delay and
adjustable overrun time.
●
F model
: Barrier-free. With light control for
rooms without windows (min. switch-on
brightness 30 lx, max. switch-off bright-
ness on unit 0.3 lx). With start delay
(50 sec.) and overrun time (6 min.).
●
G model
: With base load circuit.
Continuous operation at 35 m³/h, high
speed (full load) can be switched with
optional switch.
●
GVZ model
with base load circuit, start
delay and overrun time, Continuous
operation at 35 m³/h, high speed (full load)
can be switched with optional switch.
●
GVZC EC model
with base load circuit
and adjustable delay timing. Continuous
operation at 35 m³/h, high speed (full load)
can be switched with optional switch. The
EC variant has a particularly economical
EC motor.
●
I model
with interval control. For manual
operation with start delay and overrun
time. Operating period can be set to
between 0 and 15 hours with intervals of
around 10 minutes. Interval control off if
0 hours is set (Ti setting setting screw in
far left position). Interval control active if Ti
setting screw is turned at least 1/4 of a
turn to the right from the far left position.
●
H model
: Barrier-free. With humidity
control. Switch-on point can be set using
jumper (70 % r.h. ex factory). Overrun time
controlled by program (min. 6 minutes at
full load). Can also be operated manually
with optional switch. Not suitable for
second room ventilation.
●
D model:
In combination with three-step
switch with 3 power levels: 35, 60 or
100 m³/h. Can be used when combined
with supply air elements for controlled
domestic ventilation.
●
RC model
with radio electronics:
Use in radio-controlled ventilation system
MAICO smart. Based on EnOcean
technology. Network-compatible (master-
slave)
separate ER 100 RC operating
instructions. On/Off using radio switch or
radio control RLS RC. With 3 power levels
35, 60 or 100 m³/h.
Summary of Contents for ER-UP/G