7 Housing installation
26
7.16 ER-UP/B installation, single room
5
Metal exhaust socket with shut-off shutter
18
Main duct, steel folded spiral-seams duct
19
Connection duct, flexible aluminium duct AFR DN75/80
20
Power cable
37
UPM 60/100 mounting support
38
Plaster protective cover
39
Cable grommet
1. Remove the plaster protective cover from the
housing.
NOTICE The unit will be damaged and func-
tion impaired if the fixing screws used are in-
correctly / too long.
Fixing screws may not penetrate into the hous-
ing.
Use screws provided (mounting support
UPM 60/100).
2. For suspended ceilings, cut mounting support
to the required length, bend it into shape and
fix it to the ER-UPD housing with the supplied
screws.
3. Mark fixing holes for mounting support on ceil-
ing, drill dowel holes and insert steel dowels.
DANGER Danger of short-circuits and
damage to the unit.
If the cable grommet is not installed correctly, wa-
ter may penetrate the housing. The degree of
protection can no longer be guaranteed.
Drive through cable grommet so that it can seal
the cable sheathing all the way round (circular,
no slots).
4. Guide power cable from rear of housing
through cable grommet into housing.
5. Move housing into desired position and secure
to ceiling with both mounting supports.