17. Extraction socket ER-AS for WC odour extraction
30
17. Extraction socket ER-AS for
WC odour extraction
ER-UP/GH housing units can be connected
to the WC flushing pipe using the ER-AS
extraction socket. A Ø 70 duct cross section
facilitates low air speeds in the connecting
duct and an effective, draft-free extraction of
odours.
Pre-requirement for the connection
A Ø 70 branch must be installed in the
flushing pipe of the flush-mounted cistern.
Mounting
1. Cut the left, right or bottom housing
segment "S" out of ER-UP housing at the
marking using a knife
Fig. 8.
2. Plug ER-AS extraction socket into ER-UP
housing. The edge of the socket must click
into place on the wall of the housing.
CAUTION
Damage to unit in the event of improper
installation position of the housing floor
seal. Protection class is not
guaranteed.
Lift up the housing floor seal before
inserting the ER-AS extraction socket
and then reposition it correctly
afterwards.
3. Install ER-UP/GH housing unit in
accordance with chapter 12.1. Note the
descriptions relating to the second room
connection.
4. Connect connection duct to ER-AS
extraction socket and branch in the cistern
flushing pipe. Make sure the connections
between the connection duct and the
ER-AS extraction socket and the branch
are tight.
5. Install fan insert and cover [7]
chapter 14.
It is important that regulating plate [9]
and filter mat [10] supplied with the
ER-AS are inserted. The cover must
engage audibly when locking.
6. Run function test.