22. Wiring diagrams
43
22. Wiring diagrams
Tolerances for the times stated
below = nominal value + 20 %.
ER 60, ER 100, Centro-E
S1 On/Off switch
S1= On/Off switch
➀
= Main room
➁
= Second room
ER 60 VZ, ER 60 VZ 15,
ER 100 VZ, ER 100 VZ 15
Standard switching Switching options
S1 = On/Off
switch
(ON after approx.
50 seconds)
➀
= Main room
➁
= Second
room
ER 60 and ER 100, Centro-E
The fan starts up after switching on the room
lighting (with switch S1). The fan also
switches off after the room lighting has been
turned off.
ER 100 with main and second room
connection
The fan starts up after switching on the room
lighting (with switch S1). The fan also switches
off after the room lighting has been turned off.
ER 60 VZ, ER 60 VZ 15,
ER 100 VZ, ER 100 VZ 15
Standard switching:
The fan starts up approximately 50 seconds
after the room lighting is switched on. The fan
has an overrun time of approximately 6 mi-
nutes after switching off. With VZ 15 units,
the overrun time is approximately 15 minutes.
Switching option
The fan starts up approx. 50 seconds after
switching on the room lighting (with switch S1
and S2). The fan has an overrun time of
approximately 6 minutes after switching off
with switch S1. With VZ 15 units, the overrun
time is approximately 15 minutes. In addition,
the fan can be switched off with switch S2
independent of the room lighting.
ER 60 VZC, ER 100 VZC
The fan starts up after a start delay when the
room lighting is switched on. This can be
adjusted continuously from 0 - 150 seconds.
Depending on the setting, the fan has an
overrun time of between 1.5 and 24 minutes
after switching off. The overrun time can be
adjusted continuously from 1.5 to 24 minutes.
ER 100 VZ and ER 100 VZ 15 with
main and second room connection
The fan starts up approx. 50 seconds after
switching on the room lighting (with one
switch). The fan has an overrun time of
approximately 6 minutes after switching off
with the last switch to have been used. With
VZ 15 units, the overrun time is
approximately 15 minutes.