8 Installation
41
1. Take off frame of room air control.
2. Connect the
PPB 30 O
to the RLS 45 terminals
FAN1 and FAN 2. Connect
PPB 30 K
units to
RS 485 bus.
Information
• The power supply to the
PPB 30 K
(+) MUST
come from the Fan1 or Fan2 connection. Make
connection according to wiring diagram →
• A combination of PPB30 O and PP 45 units is
not permitted at the FAN1 and FAN2 connec-
tion terminals of the RLS control.
• No exhaust air function is possible for PPB 30
O units on an RLS 45 K control.
• If a
PPB 30 K
is running in exhaust air mode,
the
PP 45
/ PPB 30 O units handle the volumet-
ric flow compensation at the fan interface
(Fan1/Fan2). It is important that the unit type +
quantity are set correctly.
3. Insert room air control in the flush-mounted
box and screw down to flush-mounted box
with 2 screws.
4. Fit frame. Ensure that the sensor opening is
above the
PP 45 HYI
(if fitted) and that the
frame engages.
5. Commissioning ventilation system→ .
8.8 Installing radio switch (EnOcean)
When radio mode is activated, EnOcean radio
components, such as master or slave units or
sensors, can be taught-in directly on ventilation
units. For range of radio components →
Purely radio-
controlled
system
Combination system
DS 45 RC
RLS 45 K
PP 45 EO
+
+
+
PP 45 RC
PP 45 RC
PPB 30 RC
max. 6
PP 45 K
PP 45 O
PP 45 RC
PPB 30 RC
...
or
max. 3
PPB 30 O
/
PPB 30 K
Installation location: Do not mount re-
ceiver, with internal antenna, on wall side of
transmitter.
Purely radio-controlled PP 45 system
1. Simply glue
DS 45 RC
to installation location
on the wall. Alternatively, the radio switch can
also be screwed onto the wall (mounting ma-
terial provided by customer).
2. Use the "Learn button" to activate teaching-in
mode on the ventilation unit. For more detailed
information on teaching-in → Operating in-
structions.
3. For basic unit settings, such as “Block Off
function” → Installation instructions.
PushPull combination system with PP 45 EO
Extension module PP 45 EO can only be com-
bined with PP 45 RC unit pairs. Wired opera-
tion is needed for other unit types.
4. Connect EnOcean extension module to
RLS
45 K
5. Start up ventilation system, activate in
EnOcean service mode → .
PP 45 Act EnOcean actuator
With the PP 45 Act EnOcean actuator, radio-con-
trolled PP 45 RC PushPull units can be combined
with wired exhaust air units (ECA, ER). Installa-
tion similar to light switch installation; can be
switched on and off at the touch of a button. For
more information → Accessories instructions.
8.9 Installing PP 45 HYI humidity
sensor in RLS 45 O or RLS 45 K
1. Install room air control as described before.
NOTICE: Unit damage/no function if the hu-
midity sensor is installed incorrectly. Do not
bend pins. Insert sensor up to stop in bush.
Summary of Contents for PPB 30 O
Page 3: ...Steuerungskonzept PPB 30 3 Steuerungskonzept PPB 30...
Page 4: ...Steuerungskonzept PP 45 RC PPB 30 RC Funk 4 Steuerungskonzept PP 45 RC PPB 30 RC Funk...
Page 29: ...PPB 30 control concept 29 PPB 30 control concept...
Page 30: ...PP 45 RC PPB 30 RC wireless control concept 30 PP 45 RC PPB 30 RC wireless control concept...
Page 53: ...Concept de commande PPB 30 53 Concept de commande PPB 30...
Page 54: ...Concept de commande PP 45 RC PPB 30 RC radio 54 Concept de commande PP 45 RC PPB 30 RC radio...
Page 95: ...Produktdatenbl tter Product data sheets Fiches techniques du produit 95 PPB 30 O...