background image

6 Technical data

33

6 Technical data

6.1 Requirements at the installation
site

• Ambient temperature - 15 °C to + 40 °C.

• Airstream temperature, max. 40 °C.

• Max. permissible humidity in installation room of

90 % (at 20 °C, non-condensing).

• A level and solid wall surface is needed for wall

installations.

• For filter changes, ensure sufficient space to

work in front of the unit.

• Do not drill core drill hole for unit assembly and

do not drill fixing points on external and internal
covers in load-bearing components, such as in
the lintel or ring beam.

6.2 Technical data for PPB 30

External diameter

DN 160

Length of 
wall sleeve

PP 45 RHK

: 500 mm

PP 45 RHL:

 800 mm

Wall thickness

320 – 790 mm

Air filter

Filter class ISO 16890
ISO coarse 45 % (G3

) 2

items

Air volume/unit

26 m³/h

Degree of protection

IP X4

Sound pressure level:
at distance of 1 m,
free-field conditions
(ventilation levels 1 -
5)

18 / 32 / 41 / 45 / 49
dB(A)

Rated voltage

PPB 30 O

PPB 30 K

:

12 V

PPB 30 RC

: 230 V

Power frequency

50/60 Hz

Volumetric flow in
heat recovery mode,
ventilation levels
1 to 5

5 / 12 / 18 / 22 / 26 m³/h

Volumetric flow in ex-
haust air mode (no
heat recovery unit)

45 m³/h

Power consumption

1.7 / 2.5 / 3.4 / 4.4 / 5.3
W

Degree of heat provi-
sion

73.3 % (level 3)

SPI

0.19 W / (m³/h)

SEC value

A (-39,71 kWh / (m²*a))

Permissible ducting
lengths with wired
connection

From star point, max.
25 m per ventilation unit

Weight of slide-in
module, cpl.

3.6 kg

Radio components:
Frequency range

 

(in

acc. with
EN 300220-1)

868.35 MHz

Radio receiver with in-
ternal antenna

Do not mount on the
wall side of the trans-
mitter

Summary of Contents for PPB 30 O

Page 1: ...instructions for final installation kit Notice de montage Kit de montage final PushPull L ftungssysteme PushPull ventilation systems Installations de ventilation PushPull PPB 30 O PPB 30 K PPB 30 RC...

Page 2: ...gebundene Syste me 14 8 7 2 Funkgesteuerte Systeme 14 8 7 3 Anschl sse 14 8 7 4 RLS 45 O anschlie en 14 8 7 5 RLS 45 K anschlie en 15 8 8 Montage Funkschalter EnOcean 15 8 9 Einbau Feuchtesensor PP 45...

Page 3: ...Steuerungskonzept PPB 30 3 Steuerungskonzept PPB 30...

Page 4: ...Steuerungskonzept PP 45 RC PPB 30 RC Funk 4 Steuerungskonzept PP 45 RC PPB 30 RC Funk...

Page 5: ...uftfilter und Frontabdeckung Ger teeinschub inkl 2x Ventilatoreinheit und 2x Keramik W rme bertrager 1 Verl ngerungsrohr 200 mm lang 1 Zentrie rungsring 2 Dichtungsb nder 1 Bohrschablone Innengeh use...

Page 6: ...tungsger ten PPB 30 K Bad und PP 45 Wohnr ume Das PPB 30 im Badezimmer be und entl ftet gleichzeitig den Raum im balancierten Betrieb Ein Ventilator im Ger t entl ftet und bertr gt die Abluftw rme zun...

Page 7: ...olumen Ger t 26 m h Schutzart IP X4 Schalldruckpegel Ab stand 1 m Freifeldbe dingungen L ftungs stufe 1 5 18 32 41 45 49 dB A Bemessungsspan nung PPB 30 O PPB 30 K 12 V PPB 30 RC 230 V Netzfrequenz 50...

Page 8: ...S 485 Bus I2C Bus RS 485 Bus K1 2 1 0 3 0 1 0 1 K2 3 1 0 3 0 1 0 1 K3 4 1 0 3 0 1 0 1 K4 5 1 0 3 0 1 0 1 K5 6 1 0 3 0 1 0 1 K6 1 1 0 3 0 1 0 1 K7 2 1 0 3 0 1 0 1 K8 3 1 0 3 0 1 0 1 K9 1 0 3 0 1 0 1 K1...

Page 9: ...1 K27 3 0 3 0 1 Zusatzfunktionen K25 Abluftbetrieb m glich bei 1x PPB 30 O RLS 45 O Zum Start die optionale Taste L f tungsstufe 2 Sekunden dr cken 7 3 EnOcean Kombinationen K30 Funk L ftungsger t Sen...

Page 10: ...Bus der RLS 45 K Steuerung angeschlossen Bei Ver wendung mehrerer PPB 30 K an einer RLS 45 K sind die PPB 30 K Ger te ber den auf der Platine befindlichen DIP Schalter zu adressie ren Adresse 0 Ger t...

Page 11: ...in Montageanleitung Rohbau 1 Die Wandh lse ist so installiert dass sie 5 10 mm ber den Fertigputz der Au en wand hinaussteht und ein Gef lle von 1 bis 2 zur Au enwand hin aufweist Die H lse muss zur W...

Page 12: ...ungsring m glichst weit innen po sitioniert ist Eventuell den Zentrierungsring mit Klebeband auf der Wandh lse fixieren 3 Bei Verl ngerung PPB 30 VS zwei Zentrie rungsringe verwenden Die Dichtungsband...

Page 13: ...tine einste cken Die Stecker sind kodiert und vertausch sicher Anschlussleitungen in den vorgesehe nen Schlitz im Geh use einlegen Bei PPB 30 K PPB 30 RC Ger ten darauf achten dass der Feuchtesensor f...

Page 14: ...bauseitig Litzen der Anschlussleitungen ausreichend abisolieren 8 7 Raumluftsteuerungen anschlie en F r RLS 45 O RLS 45 K Steuerungen mit 230 V die Sicherheitsvorschiften beachten Elektrischer Anschl...

Page 15: ...Raumluftsteuerung in die UP Dose einsetzen und mit 2 Schrauben mit der UP Dose ver schrauben 4 Rahmen anbringen Darauf achten dass die Sensor ffnung ber dem PP 45 HYI falls ein gebaut liegt und der Ra...

Page 16: ...Einbau und Verdrahtung eines externen Sen sors PP 45 PPB 30 Installations und Inbe triebnahmeanleitung 9 Inbetriebnahme Grundeinstellungen werden an der Raumluft steuerung im Service Mode vorgenommen...

Page 17: ...D den aktuell eingestellten Parameter Parameterwert ndern Hat man ein bestimmtes Untermen erreicht k n nen mit die sen Tasten die Parame ter eingestellt werden Nach der n derung des Parameters blinken...

Page 18: ...n2 1 2 3 4 5 1 Ger tepaar PP 45 oder 1 PPB 30 2 Ger tepaare PP 45 oder 2 PPB 30 3 Ger tepaare PP 45 oder 3 PPB 30 Ungerade Anzahl 3 Ger te PP 45 Ungerade Anzahl 5 Ger te PP 45 Hier wird die Anzahl der...

Page 19: ...Einstellwert 2 An RLS 2 Einstellwert 4 und an RLS 3 Einstellwert 5 set zen Achtung Es sind nur sortenrei ne RLS Kombinationen zul s sig Sensoren 0 1 2 3 4 5 6 7 Kein Sensor 1 Sensor intern 1 Sensor in...

Page 20: ...er ModBus akiviert und die Bau drate gesetzt Achtung Bei aktiver Modbus Schnittstelle ist der Anschluss von exter nen Sensoren LTs RLS nicht m glich ModBus Adresse 1 2 3 4 5 6 7 Adresse 10 Adresse 11...

Page 21: ...aare PP 45 oder 2 PPB 30 3 Ger tepaare PP 45 oder 3 PPB 30 Ungerade Anzahl 3 Ger te PP 45 Ungerade Anzahl 5 Ger te PP 45 Hier wird die Anzahl der an der L fterschnittstelle Fan1 Fan2 angeschlossenen G...

Page 22: ...weitern Beispiel An RLS 1 werden zwei weitere RLS RLS 2 und 3 angeschlos sen Einstellwert 2 An RLS 2 Einstellwert 4 und an RLS 3 Einstellwert 5 setzen Achtung Es sind nur sorten reine RLS Kombination...

Page 23: ...en extern 0 Sensor intern 3 Sensoren extern W hlen Sie aus wie viele in terne und externe Sensoren angeschlossen kombiniert sind Zur Verf gung stehen der interne Sensor PP 45 HYI und die externen Sens...

Page 24: ...ModBus aktiv 9600 Baud ModBus aktiv 19200 Baud Mit diesem Einsteller wird der ModBus akiviert und die Bau drate gesetzt Achtung Bei aktiver Modbus Schnittstelle ist der Anschluss von PPB 30 K oder vo...

Page 25: ...nnen die Grenzwerte des integrierten Feuchtesensors eingestellt werden bzw kann er deaktiviert werden Die orange Betriebsarten LED blinkt zy klisch je 3x L ftungsstufen 0 1 L ftungsstufe Aus m glich...

Page 26: ...linkt zy klisch je 2x Einschlaffunkti on 1 2 3 30 Minuten rote LED 1x 60 Minuten rote LED 2x 90 Minuten rote LED 3x Hier wird die Dauer der Einschlaffunktion Stu fe 0 parametriert Werkseinstellung 60...

Page 27: ...0192 0758 0000 11 Umweltgerechte Entsorgung Altger te und Elektronikkomponenten d r fen nur durch elektrotechnisch unterwiesene Fachkr fte demontiert werden Eine fachge rechte Entsorgung vermeidet neg...

Page 28: ...s 40 8 7 4 Connecting RLS 45 O 40 8 7 5 Connecting RLS 45 K 40 8 8 Installing radio switch EnOcean 41 8 9 Installing PP 45 HYI humidity sensor in RLS 45 O or RLS 45 K 41 9 Commissioning 42 9 1 Service...

Page 29: ...PPB 30 control concept 29 PPB 30 control concept...

Page 30: ...PP 45 RC PPB 30 RC wireless control concept 30 PP 45 RC PPB 30 RC wireless control concept...

Page 31: ...of delivery depends on system con figuration PPB 30 O PPB 30 K PPB 30 RC ventilation unit Internal cover complete Housing 2x G3 air fil ter and front cover Slide in module including 2 fan units and 2...

Page 32: ...solution for a 3 room flat with PPB 30 K ventilation units for the bathroom and PP 45 ventilation units for living spaces The PPB 30 in the bathroom ventilates and ex tracts air from the room at the s...

Page 33: ...790 mm Air filter Filter class ISO 16890 ISO coarse 45 G3 2 items Air volume unit 26 m h Degree of protection IP X4 Sound pressure level at distance of 1 m free field conditions ventilation levels 1 5...

Page 34: ...EnOcean extension module PP 45 EO Combina tion no Interface Fan1 Fan2 Interface Fan1 Fan2 RS 485 bus 230 V in put on RLS 45 K RS 485 bus I2C bus RS 485 bus K1 2 1 0 3 0 1 0 1 K2 3 1 0 3 0 1 0 1 K3 4 1...

Page 35: ...n wire less K30 Any 1 0 8 Additional functions K30 Any number provided they are within range Supply air only from 2 PP 45 RC units Only wired exhaust air units are permitted do not use RC exhaust air...

Page 36: ...s for ventilation unit connecting cables Connection terminals can be taken off for wir ing When using the sensor based automatic dehu midification function exhaust air mode runs un til the humidity fa...

Page 37: ...stop on the external cover Ensure that the centring ring is posi tioned as far inside as possible With PPB 30 VS extension use two centring rings position as far inside and outside as pos sible 5 Tak...

Page 38: ...it can tightly seal the power cable The cable grommet must be correctly attached in the housing 6 If using PPB 30 K units and connection of an optional button or switch the second input is used with t...

Page 39: ...ructions DANGER Danger of electric shock Before installing the electrics shut down all sup ply circuits switch off mains fuse secure against being accidentally switched back on and position a visible...

Page 40: ...ns or installation instructions The relevant ventilation units are connected to the relevant room air controls power units The connection of the ventilation units to an RLS 45 O RLS 45 K generally tak...

Page 41: ...45 RC PPB 30 RC max 6 PP 45 K PP 45 O PP 45 RC PPB 30 RC or max 3 PPB 30 O PPB 30 K Installation location Do not mount re ceiver with internal antenna on wall side of transmitter Purely radio control...

Page 42: ...d in the online commissioning instructions download at www maico ventil atoren com Here you can also download the commissioning software for the RLS 45 K control This provides you with a wide range of...

Page 43: ...face Number of device pairs devices on RLS Fan1 Fan2 1 2 3 4 5 1 PP 45 or 1 PPB 30 unit pair 2 PP 45 or 2 PPB 30 unit pairs 3 PP 45 or 3 PPB 30 unit pairs Odd number 3 PP 45 units Odd number 5 PP 45 u...

Page 44: ...inations are permitted Sensors 0 1 2 3 4 5 6 7 No sensor 1 internal sensor 1 internal sensor 1 external sensor 1 internal sensor 2 external sensors 1 internal sensor 3 external sensors 0 internal sens...

Page 45: ...01 Upper and lower LEDs light up 9 3 RLS 45 K service menu Bold Factory settings LED flashes quickly LED flashes slowly LEDs Parameters Set value ventilation level Setting description Device type on R...

Page 46: ...ion without further LTs RLS Operation with 1 LT or RLS Operation with 2 LTs or RLS Operation with 3 LTs or RLS Slave no 1 Slave no 2 Slave no 3 Adjuster for adding further room air controls RLS or pow...

Page 47: ...ernal sensors 0 internal sensors 1 external sensor 0 internal sensors 2 external sensors 0 internal sensors 3 external sensors Select how many internal and external sensors are connec ted combined The...

Page 48: ...nterface here ModBus settings 1 2 3 RS 485 inactive ModBus act ive 9600 Baud ModBus active 19200 Baud This adjuster activates the ModBus and sets the baud rate Notice When the Modbus in terface is act...

Page 49: ...The limit values of the integrated humidity sensor can be set or deactivated here The orange operating mode LED flashes 3x per cycle Ventilation levels 0 1 Ventilation levels Off possible red LED OFF...

Page 50: ...D flashes 2x per cycle Sleep function 1 2 3 30 minutes red LED 1x 60 minutes red LED 2x 90 minutes red LED 3x The duration of the sleep function level 0 is parameterised here factory setting 60 minute...

Page 51: ...exten sion set 0192 0758 0000 11 Environmentally responsible disposal Old devices and electronic components may only be dismantled by specialists with elec trical training Proper disposal avoids detri...

Page 52: ...Raccordements 65 8 7 4 Raccordement de la RLS 45 O 65 8 7 5 Raccordement de la RLS 45 K 65 8 8 Montage de l interrupteur radio En Ocean 66 8 9 Installation du d tecteur d humidit PP 45 HYI dans RLS 45...

Page 53: ...Concept de commande PPB 30 53 Concept de commande PPB 30...

Page 54: ...Concept de commande PP 45 RC PPB 30 RC radio 54 Concept de commande PP 45 RC PPB 30 RC radio...

Page 55: ...syst me Appareil de ventilation PPB 30 O PPB 30 K PPB 30 RC Capot int rieur complet bo tier 2x filtre air G3 et cache de protection avant Module d insertion avec 2x unit de ventilateur et 2x caloport...

Page 56: ...ventilation dans un appartement 3 pi ces avec appareils de ventilationPPB 30 K salle de bains et PP 45 pi ces d habitation Le PPB 30 dans la salle de bains insuffle et va cue simultan ment l air de la...

Page 57: ...otection IP X4 Niveau de pression acoustique distance 1 m conditions de champ libre niveau de ventilation 1 5 18 32 41 45 49 dB A Tension de service PPB 30 O PPB 30 K 12 V PPB 30 RC 230 V Fr quence du...

Page 58: ...s RS 48 5 Bus I2C Bus RS 48 5 K1 2 1 0 3 0 1 0 1 K2 3 1 0 3 0 1 0 1 K3 4 1 0 3 0 1 0 1 K4 5 1 0 3 0 1 0 1 K5 6 1 0 3 0 1 0 1 K6 1 1 0 3 0 1 0 1 K7 2 1 0 3 0 1 0 1 K8 3 1 0 3 0 1 0 1 K9 1 0 3 0 1 0 1 K...

Page 59: ...ue si c est port e Arri v e d air seulement de 2 appareils PP 45 RC Seuls des appareils d air sortant c bl s sont ad mis n utiliser aucun appareil d air sortant RC 8 Montage 8 1 Consignes de montage N...

Page 60: ...la platine de l appareil de ventilation Commande d air ambiant RLS avec bornes de raccordement enfichables pour c bles de rac cordement des appareils de ventilation Bornes de raccordement pouvant tre...

Page 61: ...des d tecteurs et accessoires doivent tre pos s dans les tubes vides Pour raccourcir le tube de prolongation pro c der comme suit 4 Bague de centrage 5 Tube de prolongation 6 Bague de centrage 4 Intr...

Page 62: ...s de centrage jusqu la but e de la protection externe dans la gaine murale Veiller ce que la bague de centrage soit po sitionn e le plus loin possible vers l int rieur Fixer ventuellement la bague de...

Page 63: ...Appareils PPB 30 K 2 Appareils PPB 30 K 3 13 Poser le cache de l unit lectronique et le vis ser 2 vis 14 Brancher la fiche 8 p les des deux c bles de raccordement du ventilateur directement sur la pl...

Page 64: ...2 AVERTISSEMENT Risque d lectrocution en cas d une installation des appareils de ventilation l int rieur de la zone de protec tion Installation d appareils dans les zones de protec tion pr d finies se...

Page 65: ...r e et la visser avec 2 vis dans la bo te encastr e 4 Poser le cadre Veiller ce que l ouverture du d tecteur soit au dessus du PP 45 HYI si mont et que le cadre s encliquette Mettre le syst me de vent...

Page 66: ...n Arr t Notice d ins tallation Syst me combin PushPull avec PP 45 EO Module d extension PP 45 EO uniquement combinable aux paires d appareils PP 45 RC Les autres types d appareils doivent tre c bl s 4...

Page 67: ...l charger le logiciel de mise en ser vice pour la commande RLS 45 K Ce logiciel vous offre plusieurs param tres de r glage pour une adaptation individuelle du syst me 9 1 Mode Service Commande D marra...

Page 68: ...escription Type d appareil sur RLS Fan1 Fan2 1 2 PP 45 PPB 30 O La gamme de type qui est rac cord e l interface de ventila teur Fan1 Fan2 est s lection n e ici Attention seules les combinai sons d app...

Page 69: ...ED clignote rapidement LED clignote lentement LED Param tre Valeur de r glage Affi chage binaire R glage Description l ments de puissance LT ou commandes d air ambiant RLS 0 1 2 3 4 5 6 Fonctionnement...

Page 70: ...ge 5 est affich comme 101 Les LED sup rieure et inf rieure sont allum es Gras R glage usine LED clignote rapidement LED clignote lentement LED Param tre Valeur de r glage Affi chage binaire R glage De...

Page 71: ...ppareils reli s RLS Fan1 Fan2 1 2 3 4 5 1 paire d appareils PP 45 ou 1 PPB 30 2 paires d appareils PP 45 ou 2 PPB 30 3 paires d appareils PP 45 ou 3 PPB 30 Nombre impair 3 appareils PP 45 Nombre impai...

Page 72: ...ir ambiant RLS ou l ments de puissance LT Exemple deux autres RLS RLS 2 et 3 sont rac cord es la RLS 1 Valeur de r glage 2 Choisir sur RLS 2 la valeur de r glage 4 et sur RLS 3 la valeur de r glage 5...

Page 73: ...teur externe 0 d tecteur interne 2 d tec teurs externes 0 d tecteur interne 3 d tec teurs externes S lectionnez combien de d tecteurs internes et externes sont raccord s combin s Le d tecteur interne...

Page 74: ...r le ModBus et de r gler le taux de transfert Attention Si l interface Mod bus est active il est impos sible de raccorder PPB 30 K ou des d tecteurs externes LT RLS Adresse ModBus 1 2 3 4 5 6 7 Adress...

Page 75: ...LED orange de mode de fonc tionnement cli gnote 3x de fa on cy clique Niveaux de ven tilation 0 1 Niveau de ventilation Arr t possible LED rouge TEINTE Niveau de ventilation Arr t verrouill LED rouge...

Page 76: ...n cyclique Dur e d utilisa tion du filtre 1 2 3 4 2 mois LED rouge 1x 3 mois LED rouge 2x 6 mois LED rouge 3x Remise z ro de la dur e d utilisation du filtre LED rouge 4x La dur e d utilisation du fil...

Page 77: ...ctrotechnique Une li mination dans les r gles de l art vite les effets n gatifs sur l homme et l environnement et permet un recyclage de mati res premi res pr cieuses tout en minimisant l impact sur l...

Page 78: ...er components Dimensi ons d autres composants DE Komponente Abmessungen BxHxT Raumluftsteuerung RLS 45 O RLS 45 K 80 x 80 x 49 mm Funkschalter DS 45 RC 80 x 80 x 15 mm EnOcean Erweiterungs modul PP 45...

Page 79: ...ntage carts de per age 79 FR Composant Dimensions lxhxp Commande d air ambi ant RLS 45 O RLS 45 K 80 x 80 x 49 mm Interrupteur radio DS 45 RC 80 x 80 x 15 mm Module d extension EnOcean PP 45 EO 80 x 8...

Page 80: ...ms Sch mas de raccor dement et de c blage 80 Anschluss und Verdrahtungspl ne Connection and wiring diagrams Sch mas de raccordement et de c blage Anschlussplan RLS 45 K PPB 30 K Connection diagram for...

Page 81: ...n switch for additional function sleep mode intensive mode sup ply air mode safety function UP L Flush mounted distributor for connection of ventilation units Connection of all ventilation units in a...

Page 82: ...und Verdrahtungspl ne Connection and wiring diagrams Sch mas de raccor dement et de c blage 82 Anschlussplan RLS 45 O PPB 30 O Connection diagram for RLS 45 O PPB 30 O Sch ma de raccordement RLS 45 O...

Page 83: ...W F2 Fan 2 Control line for Fan 1 Fan 2 Re commended control cable J Y ST Y 2x2x0 8 mm Max length to distributor 4m W1 X Fan unit control cable Recommen ded control cable J Y ST Y 2x2x0 8 mm Max cabl...

Page 84: ...d Verdrahtungspl ne Connection and wiring diagrams Sch mas de raccor dement et de c blage 84 Anschlussplan RLS 45 K Systembus Connection diagram for RLS 45 K System bus Sch ma de raccordement RLS 45 K...

Page 85: ...u den Senso ren RLS LTs und EnOcean Modul ca 100 m Alternativ kann dieser Anschluss auch als ModBus RTU Schnittstelle ver wendet werden EN RLS 45 K PushPull 45 Comfort room air control PP 45 LT PP 45...

Page 86: ...ave 1 Fan 4 1 4 3 Appareil de ventilation 8 10 12 sur RLS esclave 2 Fan 5 1 5 3 Appareil de ventilation 13 15 17 sur RLS esclave 2 Fan 6 1 6 3 Appareil de ventilation 14 16 18 sur RLS esclave 2 S1 Bou...

Page 87: ...d Verdrahtungspl ne Connection and wiring diagrams Sch mas de raccor dement et de c blage 87 Anschlussplan RLS 45 O Systembus Connection diagram for RLS 45 O System bus Sch ma de raccordement RLS 45 O...

Page 88: ...5 HY PP 45 humidity sensor for flush mounting PP 45 CO2 PP 45 CO2 sensor for flush mounting PP 45 VOC PP 45 VOC sensor for flush mounting X1 1 Mains connection terminal RLS 45 O X1 2 Fan bus connector...

Page 89: ...le jusqu aux d tecteurs RLS LT et module EnOcean env 100 m Ce raccor dement peut aussi tre utilis comme interface Modbus RTU Anschlussplan PPB 30 K Ger teanschluss Connection diagram for PPB 30 K Unit...

Page 90: ...ctions ex haust air mode intensive ventilati on recommended control cable LiYY 2x0 5 mm Max cable length 25 m FR PPB 30 K Appareil de ventilation PPB 30 K VAP K Platine de raccordement de l appareil C...

Page 91: ...ccordement de l appareil DE PPB 30 O L ftereinheit PPB 30 Objekt VAP O Ger teanschluss Platine Objekt PPB 30 Fan1 Anschlussleitung Ventilator 1 PPB 30 Fan2 Anschlussleitung Ventilator 2 W PPB O Anschl...

Page 92: ...int FR PPB 30 O Unit de ventilation PPB 30 Objet VAP O Platine de raccordement de l appareil Objet PPB 30 Fan1 C ble de raccordement du ventila teur 1 PPB 30 Fan2 C ble de raccordement du ventila teur...

Page 93: ...Fan 2 connecting cable S1 Exhaust air mode intensive ventilati on button selection of function ser vice mode W1 PPB 30 RC mains connecting cable recommended connecting cable NYM J 3x1 5 mm W2 Connecti...

Page 94: ...Produktdatenbl tter Product data sheets Fiches techniques du produit 94 Produktdatenbl tter Product data sheets Fiches techniques du produit PPB 30 O PPB 30 K PPB 30 RC mit with avec PP 45 HYI...

Page 95: ...Produktdatenbl tter Product data sheets Fiches techniques du produit 95 PPB 30 O...

Page 96: ...Maico Elektroapparate Fabrik GmbH Steinbeisstr 20 78056 Villingen Schwenningen Deutschland Service 49 7720 6940 info maico de 0185 1229 0003_RLF 9_04 22_DSW AS...

Reviews: