12.0 CHANGING COMPONENTS
32
12.8
Gas Valve
(Fig. 66)
1. Undo the nut on the gas feed pipe under the boiler.
2. Completely undo the securing screws and hinge the
facia panel down.
3. Disconnect the earth wire and pressure sensing pipe
from the valve. Undo the screw securing the electrical
plug to the valve and disconnect the plug. Disconnect
the wires from the valve modulator.
4. Pull the earth wire off the spade terminal on the
valve.
5. Remove the screws securing the inlet pipe flange to
the boiler bottom panel and those securing the outlet
manifold to the burner manifold.
6. Remove the valve from the boiler.
7. Note the orientation of the inlet pipe and outlet
manifold. Undo the securing screws and remove the
pipe and manifold.
8. Examine the ‘O’ ring seals for damage, replacing as
necessary.
9. Fit the inlet pipe and outlet manifold to the new
valve, ensuring that the ‘O’ ring seals are in place.
10. Reassemble in reverse order and check the burner
pressure (Section 9.2).
12.9
Temperature Sensor
(Fig. 67)
1. Ease the retaining tab on the sensor away and
disconnect the electrical plug.
2. Unscrew the sensor from it’s pocket and reassemble
in reverse order. The plug will only fit one way.
12.10
Safety Thermostat
(Fig. 67)
1. Pull the two electrical connections off the
thermostat.
2. Remove the screws securing the thermostat to the
mounting plate on the flow pipe.
3. Reassemble in reverse order. The thermostat is not
polarised - either wire can fit either terminal on the
thermostat.
Temperature
Sensor
Safety
Thermostat
Flow Pipe
Fig. 66
Fig. 67
Gas Valve
Inlet Pipe
Gas Feed
Pipe
Earth Wire
Electrical
Plug
Modulator
Wires
Electrode
Lead
Earth
Wire