Prerequisites for installing a pellet boiler
11
5
5
Prerequisites for installing a pellet boiler
You must fulfill the following conditions before operating a fully automatic pellet boiler.
5.1 Guidelines and standards for installing a pellet boiler
Overview of standards and guidelines applying to the installation of a pellet boiler.
Check whether you need to obtain planning permission or approval from the authorities for installing a new
heating system or changing your existing system. Legislation in your country must be observed.
Flue gas system
EN 13384–1
Legislation in your country must be observed.
Building and fire pre-
vention regulations
Legislation in your country must be observed.
Type of installation
FC 42x
Fireplace with a flue gas fan for connection to an air exhaust sys-
tem. The combustion air line from air shaft and the connecting
piece to the chimney are part of the fireplace.
FC 52x
Fireplace with a flue gas for connection to a chimney. The com-
bustion air line from outside and the connecting piece to the
chimney are part of the fireplace.
Sound insulation
DIN 4109
Please note the building-unique demands on sound insulation.
5.2 Installation room
The installation room of the boiler is not necessarily a boiler room. Observe the applicable national and regio-
nal regulations.
1.
Safety warnings for the installation room
R
Riissk
k o
off ffiirre
e
Do not store flammable materials or liquids in the vici-
nity of the pellet boiler.
Do not permit unauthorized persons to enter the boiler
room - Keep children away.
Do not operate with fuel loading or ash removal doors
open.
2.
Ventilation of the installation room
The installation room must have air inlet and outlet openings for ventilation, even if there is a direct con-
nection to the burner for combustion air.
This is to keep the combustion zone at a neutral pressure.
3.
Admission of combustion air,
the pellet boiler requires combustion air. The combustion air can be supplied by:
a. Relying upon the boiler room air as supplied by the air inlet and outlet openings for ventilation in the
installation room.
b. Independently of the room air via a separate air intake line with a direct connection to the outdoor
atmosphere.
The air intake line must not follow the sewage pipe. The diameter of the air intake line must be at least
4 inches. If the air line is greater than 12 feet in length, or if it has more than 270 degrees of turns, then
it should be increased in size to 5 inch.
Never operate the pellet boiler if the air intake openings are partially or completely closed.
Contaminated combustion air can cause damage to the pellet boiler. Never store or use cleaning deter-
gents containing chlorine, nitrobenzene or halogen in the room where the heating system is installed, if
combustion air is drawn directly from the room. Be particularly cautious around swimming pools and
Operating Manual AutoPellet® PES 20, 32, 56
Summary of Contents for PES 20
Page 26: ...PE 568 USA 2 0 26 Setting language date and time at Pelletronic Touch...
Page 32: ...Menu navigation of Pelletronic Touch PE 568 USA 2 0 32 Main Menu...
Page 57: ...Favorite 57 Operating Manual AutoPellet PES 20 32 56...
Page 92: ...PE S K B 36 56 PE 568 USA 2 0 92 Cleaning the boiler every year...
Page 100: ......
Page 101: ......