Heating curve and Heating limits
41
Daytime
outside temp
Room temperature
too warm
too cold
+5 to +15°C
Decrease heating curving value by
0,2
Increase heating curving value by 0.2
Decrease base point value by 5°
Increase base point value by 5°
-20 to +5°C
Decrease heating curve value by 0.2
Increase heating curve value by 0.2
The advanced run up indicates how long the system has to heat before the start of
the heating time, to reach the adjusted
roomtemp heating
.
Room thermostat influence
If the measured room temperature deviates from the set room temperature, the heating controller corrects
the flow temperature with the Room thermostat influence.
The Room thermostat influence indicates how much the flow temperature is raised or lowered so that the Set
room temperature is reached.
Example:
Room temperature desired
value = 20°C
Room temperature actual va-
lue = 18°C
Temperature difference 2°C
Room sensor influence = 3
Room sensor influence
*
Temperature difference
=
Advanced run up rise/reduction
3
*
2
=
6°C
Operating Manual AutoPellet® PES 20, 32, 56