13.1a Sensors KTY2K - Heating cont Boiler Controller (Fault 1001 to 1020 and 5000 to 5007) – Sen-
sor break
Type of fault
Sensor break
Code:
1001
HC1 Flow BC
X4
1002
DHW1 OnSensor BC
X6
1003
Outside Sensor BC
X2
1004
Boiler Sensor BC
X3
1008
TPO1 BC
X7
1009
TPM1 BC
X8
1011
TPU1 BC
X9
1012
Flow Energy1 BS
X16
1013
Return Energy1 BS
X17
1014
ExistBoiler1 BS
X13
1017
Cascade OnSensor BC
X3
1018
Cascade OffSensor BC
X3
1019
Circulation Return1 BC
X14
1020
DHW1 Off Sensor BC
X6
5000
PE1 Reserve sensor1 BS
R1
5002
PE1 Reserve sensor2 BS
R2
5004
PE1 Outside sensor BS
AF
5006
PE1 Boiler sensor BS
KF
Description:
Measuring circuit of KTY sensor is open
Cause and Remedy:
sensor not connected
►
connect sensor, check plug
sensor defect
►
measure sensor (approx. 2k
Ω
at
77 °F) replace if required
sensor cable defect
►
replace sensor
sensor temperature too high
►
sensor temperature above mea-
suring range (>230 °F)