13.7 Motor turbine (Fault 5018)
Display:
[5018] PE Motor Turbine
Description:
Vaccuum turbine not running (Exit VAK)
Cause and Remedy:
Motor unplugged
►
Plug in motor, check cable connections
Motor defect
►
Replace motor
Fuse F1, suction circuit
board defective
►
Replace fuse
13.8 Output 230V (Fault 5019, 5022, 5023)
Display:
[5019] PE Ignition
[5022] PE Magnetic valve
[5023] PE Motor cleaning
Description:
No function of output ZUEND (Ignition)/MA (Magnetic valve)/ RM (Motor
cleaning)
Cause and Remedy:
Output unplugged
►
Connect plug, check cable wiring
Current value above the
maximal Limit
►
Check limits
Current value under the
minimal Limit
►
Check limits
13.9 Output 230V-2 (Fault 5020, 5024, 5025, 5027, 5029, 5030)
Display:
[5020] PE Motor ashbox (Output AV)
[5024] PE Flue gas fan (Output SZ)
[5025] PE Cirkulationspump (Output UW)
[5027] PE Motor ext auger2 (Output RES2)
[5029] PE Motor boiler auger (Output ES)
[5030] PE Combustion Fan (Output LUFT)
Description:
No function of the respective motor/pump/fan
Cause and Remedy:
Motor/pump/fan
unplugged
►
Connect plug, check cable wiring
Motor/pump/fan defect
►
Replace motor/pump/fan
13.10 Zwischenbehälter leer - Motor res 1 (Fault 5021)
Display:
[5021] PE Hopper empty / Motor RES1 (for 36-56 kW, Pellematic Condens
or PEB)
Description:
No function of PE motor res 1
Cause and Remedy:
Motor unplugged
►
Plug in motor, check cable connections
Motor defect
►
Replace motor
No pellets available
►
Refill storage-Room / supply tank
Operating Manual AutoPellet® PES 20, 32, 56
Summary of Contents for PES 20
Page 26: ...PE 568 USA 2 0 26 Setting language date and time at Pelletronic Touch...
Page 32: ...Menu navigation of Pelletronic Touch PE 568 USA 2 0 32 Main Menu...
Page 57: ...Favorite 57 Operating Manual AutoPellet PES 20 32 56...
Page 92: ...PE S K B 36 56 PE 568 USA 2 0 92 Cleaning the boiler every year...
Page 100: ......
Page 101: ......