45
114
4
DHW Return pump
DHW Return pump
is in the Main Menu.
The Return pump enables the immediate DHW
tap of the water taps. DHW Return pump has
following menu items:
• Mode
• Switch off temperature
• Switch on hysteresis
• Time allocation
• Values
• Time 1
• Time 2
Off
Auto
DHW Return pump inactive
Temperature regulation within the time programme
If the return temperature sensor of the DHW Return pump reaches the
Switch
off temperature
, the pump switches off.
If the return temperature falls below the switch off temperature – the DHW
Return pump switches on again!
Choose the time programme 1 or 2.
You see all the DHW pump corresponding measuring values.
Set the run times of the Return pump. The return pump – time programme
works the same way like the heating circuit time programme.
Note:
A
Return Pump
and a
booster
rule out each other.
Operating Manual AutoPellet® PES 20, 32, 56
Summary of Contents for PES 20
Page 26: ...PE 568 USA 2 0 26 Setting language date and time at Pelletronic Touch...
Page 32: ...Menu navigation of Pelletronic Touch PE 568 USA 2 0 32 Main Menu...
Page 57: ...Favorite 57 Operating Manual AutoPellet PES 20 32 56...
Page 92: ...PE S K B 36 56 PE 568 USA 2 0 92 Cleaning the boiler every year...
Page 100: ......
Page 101: ......