background image

19

CR Series Woodburning Fireplaces

20001316

  Accessory

Description

Model No.

P325g

firestop 

SKFS2A

SKFS6A

3/4/99   djt

Firestop

Used to support the chimney at each 
30 feet of vertical height above the 
hearth and at every 6 feet of inclined 
chimney run. Each support adds 2

¹⁄₂ 

inches to chimney length.

Required at each floor level and attic 
on multi-story installation.

Gives traditional chimney top look 
using simulated brick in red, tan or 
white color. Brick pattern is em-
bossed into galvanized steel unit. 
Roof flashing is included. Appropri-
ate adapter is required.
See Sections 2 and 3.

Required to extend Traditional Top 
Housings on steeply pitched roofs.

Used to terminate chimney at the 
top of a chase. Flashing is not 
included. Appropriate adapter is 
required. See Sections 2 and 3.

SKCS8

(8” flue)

SKFS2A (8” straight flue)

SKFS6A (8” 30° inclined flue)

S20BR/BT/BW

202036

(single flue)

204436

(double flue)

SLTSK8

or

PLTSK8

Top Housings

Housing Extensions

P325j

Chase top housings

SLTSK8, PLTSK8

3/5/99   djt

Contemporary Chase Top 

Terminations

PLTSK8

SLTSK8

P325f-j

P325f

Chimney Support

SKCS8

3/4/99   djt

Chimney Support

P325i

housings extensions

3/4/99  djt

P325h

top housings

4/28/99  djt

Summary of Contents for CR36L

Page 1: ...CR36R CR36L CR Series Corner Woodburning Fireplace DO NOT DISCARD THIS MANUAL Retain for future use For use in U S Canada Underwriter s Laboratories Report No MH6018 20001316 4 07 Rev 14 Homeowner s Installation and Operating Manual ...

Page 2: ...ed or approved by CFM Corpo ration in combination or assembly with a CFM Corporation fireplace system notwithstanding any independent testing laboratory or other third party approval of such component parts or accessory Any such action may possibly cause a fire hazard Consult local building codes to ensure that you are in compliance before installing the fireplace Fireplaces must be vented to the out...

Page 3: ...mm 21 545mm 172mm 36 914mm 40 1019mm 1054mm Gas Line Access 9 241mm 8 203mm 7 178mm 14 362mm 4 Dia Outside Air Collar Rough Opening Height CR36R L Series Woodburning Fireplace Fig 1 CR36R L Series specifications and framing CR36R Shown 25 648 mm 25 648 mm 32 822 mm 15 397 mm 32 822 mm 15 397 mm CR36L CR36R FP1538 CR Hearth size 10 04 djt FP1538 Fig 1a CR36R L hearth dimensions ...

Page 4: ...en Grate Firebox Outside Air Control Outside Air Cover Plate Gas Access See Figure 20 on page 15 for clearance information Outer Dome Ceiling Level Firestop Batt Insulation cut out around firestop Fig 2 Fireplace and chase parts identification FP704CR Chase Installation Insulation methods shown are optional for cold climates not a requirement for unit operation Ledge Bracket ...

Page 5: ...imney exit at top CR36L R Series Maximum 90 0 Minimum Without elbows 14 0 With 2 elbows 15 0 With 4 elbows 21 0 B Do not use more than four elbows per chimney Attach the straps of the top elbows to a structural framing member The first elbow of any pair does not have straps C The chimney cannot be more than 30 from the vertical plane D The maximum length of the angled run of the total chimney syste...

Page 6: ...on the surface of the roof a distance of 10 3 m from the chimney in a horizontal plane The top of the chimney must be at least 2 610 mm above the reference point but never less than 3 914 mm in height above the high est point where it passes through the roof In planning a chimney system it is important to know 1 The height of a chimney is measured from the hearth to the exit point on the terminati...

Page 7: ...sible Insulate base of fireplace with a non combus tible insulation rated for a minimum of 300 F Insulating is very important for outside wall installations over a concrete slab If fireplace is installed on a platform insulation should be placed on top of the platform before fireplace is set Fig 7 When a fireplace is installed in a chase or on an outside wall enclosure should be treated like any outsi...

Page 8: ...rebox and indicate dimension X to locate the side wall framing Fig 8 Be sure to observe clearance requirements for side and parallel combustible walls as noted in Figure 20 Page 15 FP555CR Insulation 2 26 99 djt Hard Flat Surface Insulation Platform FP555CR Fig 7 Insulation between platform and fireplace Offset Installation In order to clear an obstruction it may be necessary to offset chimney from...

Page 9: ... strip must be fabricated and used to protect combustible surfaces in front of the fireplace This Z shaped safety strip is not provided but must be fabricated of metal with each horizontal leg at least 1 38mm wide and equal in length to the metal strips provided with the fireplace NOTE Safety strips are not required over noncombus tible floors where all supports at the base of the fire place are nonco...

Page 10: ...alling the Firestop Spacer in the Ceiling Hole A firestop spacer is used to keep pipe spaced properly and required for safety Nail the firestop spacer at each corner to the framing members of the ceiling hole NOTE A firestop spacer is not required at the roof Fig 12 Fasten fireplace in position STR100 standoffs corner 2 18 99 djt Nail Top Standoffs STR100 Fig 13 Install pipe listening for the snap loc...

Page 11: ...in insulation is planned to be used in the attic Install the attic insulation shield with the flanges on its base extending down into the framing hole Nail each corner of attic insulation shield to the framing members of the ceiling hole using 8d nails Attic shields are not required at the roof Continue Installing Pipe to Complete Run Continue attaching pipe sections to complete system to next leve...

Page 12: ... predetermined height Check the chimney top installation instructions for details on how high above the roof top the chimney sections all pipes should extend Installing Top Housing or Termination Follow the installation instructions provided with the CFM Corporation chimney termination you have se lected Installing Chimney In a Chase Refer to Page 4 Figure 2 for an illustration of a typical chase ...

Page 13: ... 159mm Min 12 305mm Max 12 305mm Max 7 16 1 1 Fig 18 Fireplace surround flush with finished wall FE101a Combustible Mantel and Trim Mantel Clearance No Noncombustible Facing Material Mantel Clearance with Noncombustible Facing Material Finished Wall Finished Wall Combustible Mantel and Trim Header Ledge Bracket Must be Sealed with Non combustible Material Top View Finished Wall Header Ledge Bracket ...

Page 14: ... Manville CERAFORM 126 K 27 1 2 thick re quired 2 CFM Corporation Building Products EH2416 K 458 1 thick required Hearth Installation A hearth extension is required to protect a combustible floor in front of the fireplace Refer to Figure 20 for mini mum dimensions and mounting detail NOTE Hearth Extension must not cover the air inlet opening of a fireplace The hearth extension described in Figure 20 ...

Page 15: ...mbustible deco rative covering OR 018 Min Sheet Metal Combustible Floor Minimum Insulation Value R Fireplace Hearth FS108 Sealing Sides 6 22 99 djt Safety Strips must be Overlapped Min Seal Crack Between Fireplace and Hearth Extension with Noncombus tible Material Minimum Insulation Value R Wall Covering Noncombustible Decorative Facing Fig 18 2x4 Header DO NOT Notch at Standoffs Seal All Cracks B...

Page 16: ...ly seal between the pipe and the tube NOTE The gas pipe should not come in contact with any wood structures until it has reached a point at least one 1 inch away from the fireplace side NOTE Local codes may require removal of flue damper when installing any type of gas appliance in a fireplace The gas pipe installation is intended for connection to a decorative gas appliance only 1 incorporating an a...

Page 17: ...842 20001183 5a Screen Rod Finished 90 7554156 7554155 5b Screen Rod Finished Straight 7554181 7554181 6 Screen Pulls two per fireplace 5584139 5584139 7a Firebrick Side 20000793 20000794 7b Firebrick Back 20000792 20000792 7c Firebrick Hearth 20000791 20000838 8 Cable Clips four per fireplace 7512135 7512135 9 Firebrick Retainers 3030172 3030172 10 Basket Grate 7579112 7579111 CFM Corporation reser...

Page 18: ...he system If you use an unapproved component or make any modifications you may possibly cause a fire hazard and will void the CFM Corporation warranty In addition such action may void the coverage provided by the owner s home insurance Accessory Description Model No P325a Glass enclosure 3 4 99 djt Designed to enclose the CR36L R Series fireplace opening with glass doors allowing the fire to remain vi...

Page 19: ...vanized steel unit Roof flashing is included Appropri ate adapter is required See Sections 2 and 3 Required to extend Traditional Top Housings on steeply pitched roofs Used to terminate chimney at the top of a chase Flashing is not included Appropriate adapter is required See Sections 2 and 3 SKCS8 8 flue SKFS2A 8 straight flue SKFS6A 8 30 inclined flue S20BR BT BW 202036 single flue 204436 double flue ...

Page 20: ... the roof Flashing not included For use with CFM Corporation Type SK8 Chimney Systems Used to terminate chimney at the top of a chase Adapter kit included Flashing not included 8 6 12 8 flue 0 to 6 12 pitch 8 12 12 8 flue 6 12 to 12 12 pitch 8 flue SK81 1 long SK818 1 long SK83 3 long SK84 4 long SK830 2 8 30 flue RLTSK8 RLTSK8L P325m Chimney elbows SK8 3 5 99 djt P325n Chimney top RLTSK8 3 5 99 djt P...

Page 21: ...25r Adapter kit CTSK42 3 5 99 djt Chase Top Adapter Kit Hearth Patching Kit 325p r P325p Chase top housings SKDSBL PKDSBL 4 28 99 djt Accessories for Canada Accessory Description Model No Attic Insulation Shield Chimney Collar Enclosure SK8 Chimney Sections 45 Chimney Elbows Used to prevent insulation from coming in contact with the chimney system Installs on the over the chimney collar of the fire...

Page 22: ...22 CR Series Woodburning Fireplaces 20001316 ...

Page 23: ... installed in the continental United States the state of Alaska and Canada only if and so long as the Fireplace is installed or serviced by a qualified installer preferably NFI or WETT Canada certified and according to the installation instructions furnished with the Fireplace and operated at all times under normal condi tions use and service according to the operative instructions furnished with th...

Page 24: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation ...

Reviews: