background image

12

SHR Series Woodburning Fireplace

20001384

Installing the Chimney System

Start by attaching the first chimney section to the collar 
on top of the fireplace.

  

Install the pipe as pictured in Figure 19.  When  you 
get a good lock, you will hear the pipe clearly snap 
together. Once sections are snap-locked in place, it is 
extremely difficult to get them apart.  

Make sure the 

pipe is firmly snapped and locked together as each 
pipe section is mounted.

When installing elbows, only outer pipe will snap- lock.  
Middle pipes simply slide into position.   Be sure to 
always attach straps on upper elbow to a structural 
framing member. (Fig. 20)
Continue installing the pipe as required until pipe is 
installed up through the ceiling.  At this point, you must 
install a firestop spacer.

FP270/271

CR Series

2/19/99   djt

ELBOW STRAP

ANGLED STRAP

Fig. 20 

 Attach straps to a structural framing member.

FP270/271

Support Structure

Elbow Strap

(must be tight)

Ceiling 

Hole 

Framing

Angle Firestop

Chimney Support 

Strap

(must be tight)

UP

FP558SHR

snap lock

5/11/99   djt

FP558SHR

Fig. 19 

 Install pipe, listening for the snap-lock to fasten.

Inner Pipe Section

Hem

Lance

Pipe 

Rim

Pipe

Rim

FP710a

SHR OUTSIDE AIR LEVER

WOOD FIREPLACES

10/21/99

Closed

Open

Fig. 18

  Outside air operation.

FP710a

Installing the Firestop Spacer 

in the Ceiling Hole

A firestop spacer is used to keep pipe spaced properly 
and required for safety.
Nail the firestop spacer (at each corner) to the framing 
members of the ceiling hole. 

Note: 

 A firestop spacer is 

not required at the roof.
Hole sizes listed in Figure 14 for angled firestop spac-
ers provide minimum required air space to chimney 
pipe for ceiling thickness up to eight (8) inches.  When 
combined thickness of ceiling material, ceiling joists and 
flooring material exceeds eight (8) inches, adjustments 
must be made in framing to assure that minimum air 
spaces to chimney are maintained.

Proper Firestop Spacer Installation

Figure 21 shows different installation procedures for  
both an area that 

is

 an attic and  an area that 

is not

 an 

attic.
If the area above the ceiling

 is not 

an attic, position the 

firestop spacer with the flange on the ceiling side and 
the angled portion extending up into the hole.
If the area above the ceiling 

is

 an attic, position the 

firestop spacer with the flange on the top of the framed 
hole and the angled portion extending down into the 
hole.
Firestop spacers are not available for, nor are they 
required on, vertical walls.
The chimney components (CF11) used on the SHR 
series fireplaces have been tested and approved with 
the area where the outer pipe slides through the firestop 
spacer sealed with a noncombustible caulk  if desired, 
or left completely open with no sealant. This sealing 
only applies to the SHR series fireplace.

Summary of Contents for SHR36

Page 1: ...HR Series Woodburning Fireplace For Models SHR36 SHR42A SHR48 SHR52 Underwriter s Laboratories Report No MH6018 DO NOT DISCARD THIS MANUAL Retain for future use 20001384 4 08 Rev 21 Homeowner s Instal...

Page 2: ...o ration in combination or assembly with a CFM Corporation replace system notwithstanding any independent testing laboratory or other third party approval of such component parts or accessory Any such...

Page 3: ...Gas Line Access Gas Line Access 1365mm FP546A Fig 2 SHR42A Series speci cations and framing SHR42A Series Woodburning Fireplace 36 914mm 46 1175mm 44 1118mm 610mm 189mm 13 Dia 340mm Rough Opening Widt...

Page 4: ...Access Gas Line Access 1518mm SHR48 Series Woodburning Fireplace Fig 3 SHR48 Series speci cations and framing FP545A 9 235mm 52 1321mm 62 1584mm 52 1334mm 838mm 189mm 13 Dia Rough Opening Width 63 Rou...

Page 5: ...att Insulation cut out around restop Firestop Ceiling Level Draftstop Ledge Bracket Surround Damper Control Gas Line Knockout both sides Screen Grate Firebox Metal Safety Strips 1 2 or 3 Outside Air C...

Page 6: ...h to the chimney exit SHR36 SHR42A SHR48 SHR52 Max 90 90 90 90 Min 0 Elbows 14 6 14 6 16 0 16 0 2 Elbows 15 6 15 6 19 0 19 0 4 Elbows 21 0 21 0 24 0 24 0 B Do not use more than 4 elbows per chim ney A...

Page 7: ...2 A chimney cannot be offset more than 30 degrees from a vertical plane 3 A chimney may run straight up or it may be neces sary to offset it to avoid obstructions 4 The maximum length of an angled run...

Page 8: ...how the chimney system should be run contact your Majes tic Fireplaces dealer for assistance Insulating Fireplace Enclosure for Cold Climates If you live in a cold climate it is not required but high...

Page 9: ...corner be hind the end of the left rebrick Push both panels back as far as possible into the left side and corner 4 Swing the right side of the back rebrick into place Attach the left brick in place u...

Page 10: ...hed by using CFM Corporation elbows Use the 30 Offset Elbow table on Page 6 to determine proper offset and parts required Each offset requires two 2 elbows The second elbow is equipped with support st...

Page 11: ...ety strips are not required over noncombus tible oors where all supports at the base of the re place are noncombustible Four 4 nailing anges are supplied with the replace found on the replace hearth T...

Page 12: ...Spacer in the Ceiling Hole A restop spacer is used to keep pipe spaced properly and required for safety Nail the restop spacer at each corner to the framing members of the ceiling hole Note A restop...

Page 13: ...te Run Continue attaching pipe sections to complete system to next level always being careful that the pipe is rmly snap locked in place before proceeding to next pipe section Chimney Supports If chim...

Page 14: ...hase installation CAUTION Treatment of restop spacers and construc tion of chase may vary with type of building These instructions are not a substitute for local building codes You must check your loc...

Page 15: ...in 1 12 305mm Max 12 305mm min 1 6 159mm Min 3 4 FP531 Fig 24 Mantel clearance Header Must be sealed with non combustible material Surround Face Finished Wall Ledge Bracket Finished Wall Ledge Bracket...

Page 16: ...front 12 20 01 djt CAUTION Do Not Place Finishing Ma terial Beyond These Edges or Cover Air Inlets Screen Rail Hearth FP1168 Fig 28 Finishing front of replace MA81 rev 8 5 97 rev 4 18 01 1 Ref MA81 F...

Page 17: ...alue of the al ternate material employed is greater than or equal to R 1 09 Thermal resistance R or thermal conductivity K may be obtained from manufacturer of the material Factors are related by the...

Page 18: ...will vary depending on thickness of noncombustible surround facing 4 Shaded area starts 1 2 away from edge of unit A B C D E F G H J SHR36 20 12 35 42 18 14 8 16 52 508 mm 305 mm 457 mm 356 mm 203 mm...

Page 19: ...Corporation replaces Be sure to have the appliance installed in accordance with building codes Gas connection may enter from either left or right side of the replace Locate appropriate gas line in the...

Page 20: ...0006021 20001431 20005569 4 Screen Rod two per replace 7554181 7554199 20001428 20005790 5 Screen two per replace 7554295 20001723 20001723 20005278 6 Screen Pull two per replace 5584139 5584139 55841...

Page 21: ...accessories for this appliance are available from your local Majestic Fireplaces distributor Should you need additional information beyond what your distributor can furnish contact CFM Corporation 269...

Page 22: ...CFM Corporation Type 11CF Chimney Systems Used to terminate chimney at top of chase Adapter kit included Flashing not included Used to build 11CF chimney systems Used to develop 30 offset chimney sys...

Page 23: ...nstalled in the continental United States the state of Alaska and Canada only if and so long as the Fireplace is installed or serviced by a quali ed installer preferably NFI or WETT Canada certi ed an...

Page 24: ...CFM Corporation 2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation...

Reviews: