background image

14

SHR Series Woodburning Fireplace

20001384

Cut and Frame Roof Hole

Size of roof hole varies with the type of chimney termi-
nation installed. Refer to installation instructions pro-
vided with the  chimney termination to find correct size 
roof hole.
There must be a 2" (51 mm) air space between out-
ermost portion of chimney sections and any adjacent 
combustible surfaces. (Combustible surfaces include 
burnable materials such as:  ceiling members, joists, 
flooring, combustible insulation and roof structures.)

WARNING:  DO NOT PACK REQUIRED AIR SPACES 
WITH INSULATION OR OTHER MATERIALS.

Mark an outline of the roof hole around the centerpoint 
of the nail. 

NOTE:

 Hole dimensions given in the chim-

ney top installation instructions are 

horizontal 

dimen-

sions; therefore, the hole size must be marked on the 
roof accordingly.
Cover the opening of the installed chimney so debris 
cannot get into the system.
Cut and frame the hole. It is good practice to use fram-
ing lumber that is the same size as the rafters.  Install 
the frame securely because the chimney top and flash-
ing anchored to the frame must be able to withstand 
heavy winds.

Install Remainder of Chimney Sections

Since you have already preplanned the height of your 
termination according to the 

Ten Foot Rule

, continue to 

install pipe to the predetermined height.
Check the chimney top installation instructions for 
details on how high above the roof top the chimney sec-
tions (all pipes) should extend.

Installing Top Housing or Termination

Follow the installation instructions provided with the 
chimney termination you have selected.

Installing Chimney in a Chase

Refer to Page 5, Figure 4 for an illustration of a typical 
chase installation.

CAUTION:

  Treatment of firestop spacers and construc-

tion of chase may vary with type of building.  These 
instructions are not a substitute for local building codes.  
You 

must

 check your local building codes to determine 

specific requirements for your city or state. 

NOTE: 

Other building materials may be required in addition to 
Firestop Spacers.

Finishing

CAUTION:  

All joints between the finished wall and 

the fireplace surround (top/sides) must be sealed with 
noncombustible material to prevent cold air leakage into 

FP559SHR

Fig. 23  

Minimum clearances to combustibles.

FP559SHR

SHR air spaces

5/12/99   djt

 

 

Air Space Clearances

Combustible framing material 

MUST NOT

 pen-

etrate AIR SPACE (shaded areas)

Standoff

2"

³⁄₄

" Air Space 

to Sides

Firestop

Front View

Side View

Wall 

Shield

3/4" Air Space 

to Back

3/4" Air Space 

to Sides

0" Clearance to Floor

Hearth Extension

Only noncombustible material 

may be applied as facing to 

the black fireplace surround.

the room. Only noncombustible material may be applied 
to the facing of the fireplace surround.  (Black painted 
area) (Fig. 23) 
The SHR52 has a framing shield between the front 
standoffs that may be used to attach finish material. 
(Fig. 25)

Finish Wall

Finish the wall with material of your choice.  

Do not 

install a combustible mantel shelf less than 12" (305 
mm) from the top of the  fireplace opening. Do not 
install a mantel face plate less than 6" (159 mm) 
from top of fireplace opening. 

(Fig. 29) If a combus-

tible material is used below a flat mantel shelf, consult 
your local building codes for minimum clearance from 
top of fireplace opening to bottom of mantel shelf.
All joints (top, bottom and sides) where wall or deco-
rative facing material meets fireplace surround must 
be completely sealed with a noncombustible material.  
(Figs. 24-29)

NOTE:

  No side wall protection is required for fireplaces 

installed at 45° to two (2) side walls (corner installation).

Summary of Contents for SHR36

Page 1: ...HR Series Woodburning Fireplace For Models SHR36 SHR42A SHR48 SHR52 Underwriter s Laboratories Report No MH6018 DO NOT DISCARD THIS MANUAL Retain for future use 20001384 4 08 Rev 21 Homeowner s Instal...

Page 2: ...o ration in combination or assembly with a CFM Corporation replace system notwithstanding any independent testing laboratory or other third party approval of such component parts or accessory Any such...

Page 3: ...Gas Line Access Gas Line Access 1365mm FP546A Fig 2 SHR42A Series speci cations and framing SHR42A Series Woodburning Fireplace 36 914mm 46 1175mm 44 1118mm 610mm 189mm 13 Dia 340mm Rough Opening Widt...

Page 4: ...Access Gas Line Access 1518mm SHR48 Series Woodburning Fireplace Fig 3 SHR48 Series speci cations and framing FP545A 9 235mm 52 1321mm 62 1584mm 52 1334mm 838mm 189mm 13 Dia Rough Opening Width 63 Rou...

Page 5: ...att Insulation cut out around restop Firestop Ceiling Level Draftstop Ledge Bracket Surround Damper Control Gas Line Knockout both sides Screen Grate Firebox Metal Safety Strips 1 2 or 3 Outside Air C...

Page 6: ...h to the chimney exit SHR36 SHR42A SHR48 SHR52 Max 90 90 90 90 Min 0 Elbows 14 6 14 6 16 0 16 0 2 Elbows 15 6 15 6 19 0 19 0 4 Elbows 21 0 21 0 24 0 24 0 B Do not use more than 4 elbows per chim ney A...

Page 7: ...2 A chimney cannot be offset more than 30 degrees from a vertical plane 3 A chimney may run straight up or it may be neces sary to offset it to avoid obstructions 4 The maximum length of an angled run...

Page 8: ...how the chimney system should be run contact your Majes tic Fireplaces dealer for assistance Insulating Fireplace Enclosure for Cold Climates If you live in a cold climate it is not required but high...

Page 9: ...corner be hind the end of the left rebrick Push both panels back as far as possible into the left side and corner 4 Swing the right side of the back rebrick into place Attach the left brick in place u...

Page 10: ...hed by using CFM Corporation elbows Use the 30 Offset Elbow table on Page 6 to determine proper offset and parts required Each offset requires two 2 elbows The second elbow is equipped with support st...

Page 11: ...ety strips are not required over noncombus tible oors where all supports at the base of the re place are noncombustible Four 4 nailing anges are supplied with the replace found on the replace hearth T...

Page 12: ...Spacer in the Ceiling Hole A restop spacer is used to keep pipe spaced properly and required for safety Nail the restop spacer at each corner to the framing members of the ceiling hole Note A restop...

Page 13: ...te Run Continue attaching pipe sections to complete system to next level always being careful that the pipe is rmly snap locked in place before proceeding to next pipe section Chimney Supports If chim...

Page 14: ...hase installation CAUTION Treatment of restop spacers and construc tion of chase may vary with type of building These instructions are not a substitute for local building codes You must check your loc...

Page 15: ...in 1 12 305mm Max 12 305mm min 1 6 159mm Min 3 4 FP531 Fig 24 Mantel clearance Header Must be sealed with non combustible material Surround Face Finished Wall Ledge Bracket Finished Wall Ledge Bracket...

Page 16: ...front 12 20 01 djt CAUTION Do Not Place Finishing Ma terial Beyond These Edges or Cover Air Inlets Screen Rail Hearth FP1168 Fig 28 Finishing front of replace MA81 rev 8 5 97 rev 4 18 01 1 Ref MA81 F...

Page 17: ...alue of the al ternate material employed is greater than or equal to R 1 09 Thermal resistance R or thermal conductivity K may be obtained from manufacturer of the material Factors are related by the...

Page 18: ...will vary depending on thickness of noncombustible surround facing 4 Shaded area starts 1 2 away from edge of unit A B C D E F G H J SHR36 20 12 35 42 18 14 8 16 52 508 mm 305 mm 457 mm 356 mm 203 mm...

Page 19: ...Corporation replaces Be sure to have the appliance installed in accordance with building codes Gas connection may enter from either left or right side of the replace Locate appropriate gas line in the...

Page 20: ...0006021 20001431 20005569 4 Screen Rod two per replace 7554181 7554199 20001428 20005790 5 Screen two per replace 7554295 20001723 20001723 20005278 6 Screen Pull two per replace 5584139 5584139 55841...

Page 21: ...accessories for this appliance are available from your local Majestic Fireplaces distributor Should you need additional information beyond what your distributor can furnish contact CFM Corporation 269...

Page 22: ...CFM Corporation Type 11CF Chimney Systems Used to terminate chimney at top of chase Adapter kit included Flashing not included Used to build 11CF chimney systems Used to develop 30 offset chimney sys...

Page 23: ...nstalled in the continental United States the state of Alaska and Canada only if and so long as the Fireplace is installed or serviced by a quali ed installer preferably NFI or WETT Canada certi ed an...

Page 24: ...CFM Corporation 2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation...

Reviews: