BOXER SERIES10-20 KVA
INSTALLATION
AG-SD-109 Publishing Date: 13.10.2015 Revision No: 0 Rev. Date:
Devices must be running on the firmware with the same version and revision codes,
devices operating with old firmware must be updated.
Devices must be located as close possible as to each other (maximum 6 * 110 cm
paralleling cables.)
Each device must have its own neutral cable.
Each device must have its own ground cable.
Devices must be connected through the distribution board and phases must be properly
connected. (U
1
-U
2
-…-U
N
), (V
1
-V
2
-…-V
N
), (W
1
-W
2
-…-W
N
).
Same battery group must not be connected to devices more than one
For equal current sharing, all cables with which the devices are connected to the board
must be equal in length and cross section.
Parallel Settings
Connect the parallel cable as shown in figure below. Only use the cables provided by MAKELSAN.