BOXER SERIES 10-20 KVA
EXPLANATIONS OF LOGGING
AG-SD-109 Publishing Date: 13.10.2015 Revision No: 0 Rev. Date:
Main Menu>Control> Switch to BYPASS
Note: The UPS will not switch to bypass mode if the mains is out of limits or phases are wrongly
connected.
4.1.3.3 Switching from Static Bypass Mode to Normal Mode
Switch the device to UPS mode via user panel. Verify the case through mimic diagram.
Main Menu>Control> Switch to UPS
Note: The inverter will not undertake the load if the inverter voltage is out of limits or there is
overload or over temperature situation.
4.1.3.4 Switching from Normal Mode to Maintenance Bypass Mode
Make sure that the inverter output is synchronized with the maintenance
bypass line before switching to maintenance bypass mode. Otherwise, there
is a possibility of cutting off the load power for a short while.
Switch the device to static Bypass mode using the front panel. Check If static
bypass led has flashed in mimic diagram.