BOXER SERIES 10-20 KVA
EXPLANATIONS OF LOGGING
AG-SD-109 Publishing Date: 13.10.2015 Revision No: 0 Rev. Date:
3. Check the UPS has switched to bypass mode, via mimic diagram LEDs and LCD panel.
4. Switch output (CB3), battery (CB4),input(CB1)and external battery (CB5) breakers to open
circuit (OFF) position respectively.
MAKE SURE THAT THERE ARE NO CRITICAL LOADS ON THE UPS OUTPUT
BEFORE PERFORMING A COMPLETE SHUTDOWN.
4.1.5 EPO (Emergency Power OFF)
By pressing the EPO button, the UPS turns the rectifier and the inverter off respectively. If the
output breaker turn off option is set, the UPS completely disconnects from the system.
4.1.6 RS232 Serial Communication Installation and Examination
Boxer series has an RS-232 interface which supports SEC and TELNET protocol as standard.
This interface is fully isolated and safe. The status of UPS can be monitored remotely via a PC or
SNMP by using this protocol. This connection works with any kind of option.