BOXER SERIES 10-20 KVA
TABLE OF TECHNICAL SPECIFICATIONS
AG-SD-109 Publishing Date: 13.10.2015 Revision No: 0 Rev. Date:
6 TABLE of TECHNICAL SPECIFICATIONS
Technical Specifications
Power
10kVA
15kVA
20kVA
Active Power
8Kw
12kW
16kW
INPUT
Input Voltage Range
220/380 VAC - %15 + %18 3P + N + PE
Input Power Factor
At Full Load > 0,99
Input Frequency Range
45-65 Hz (Selectable)
Rectifier
IGBT Rectifier
Total Harmonic Distortion
(THDi)
<4%
OUTPUT
Output Voltage
220/380 VAC 3P + N ± 1% Static, ± 1% Dynamic
Recovery
At 0% - 100% - 0% load maximum output tolerance 5%, 1%
back to band<40ms.
Efficiency
Up to 93%.
Output Frequency Range
In 50Hz ±0,5% range synchronous with the network, 50Hz ±
0,2% battery mode
Output Harmonic Distortion
(THDv)
Linear Load<2%
Non-Linear Load <6%
Crest Factor (CF)
3:1
Overload Capacity
At 125 % load 10 minutes, at 150 % load 1 minute.
Protections
The input voltage is out of tolerance, input frequency is out of
tolerance, input phase failure, output voltage is out of
tolerance, output frequency is out of tolerance, output phase
failure, DC component that can occur at the output voltage,
Overload that will occur at the output (out of the periods
specified), Overheating that will cause failure related to over
temperature, high voltage which will occur at DC bus voltage,
low voltage which will occur at DC bus voltage, short circuit at
the output.