BOXER SERIES 10-20 KVA
TABLE OF TECHNICAL SPECIFICATIONS
AG-SD-109 Publishing Date: 13.10.2015 Revision No: 0 Rev. Date:
BATTERY
Quantity (12V DC VRLA)
62 (consists of 2 independent 31 battery groups)
Charge Value ( C )
Nominal 0.1 C, selectable.
Battery Power
25% of the device power
COMMUNICATION
Communication Port
RS232 Standard, RS485 and SNMP Adapter option
Dry Contact
Optional
Protocol
SEC, TELNET
CERTIFICATES
Quality
ISO 9001
LVD/ Safety
IEC 62040-1, IEC 60950
EMC
IEC 62040-2
GENERAL
Running Temperature
0 °C ~40 °C range (for batteries 0 ~ 25 °C)
Storage Temperature
-15 °C ~ 45 °C range (for batteries -10 ~ 60°C)
Protection Class
IP20
Chassis
Anti-Static Paint Protection
Humidity
0-95 %
Operating Altitude
<1000m, Correction Factor 1. <2000m, Correction Factor
>0,92, <3000m; Correction Factor >0,84
Logging
500 detailed event log. (Status Menu is recorded)
Parallel Operation
Parallel power increase up to 8 pieces
EPO (Emergency Power Off)
Standard
Isolation Transformer
Optional
Net Weight (Without
Battery)
100 kg
100 kg
110 kg
Dimensions (W x D x H)mm
460x805x1190mm