BOXER SERIES 80-120 KVA
PRODUCT DESCRIPTION
AG-SD-37/ Publication Date: 19.10.2012/Rev. No:1/Rev. Date:16.11.2012
20
Battery Installation Date
When new batteries are installed, set the battery
install date via this menu.
Automatic Restart
In battery mode, the device operates until batteries
discharge and then shuts down. Auto-restart can be
used to restart the UPS automatically when the
mains gets back into limit values.
Open/close auto restart via the option of ON/OFF
and determine how much time after the device will
be started after the mains is normal through the time
option below.
Automatic Battery Test
Use this menu to open/close automatic battery test
and to set the period (repeat period for the regular
test) independently from user.
Screen
Change the screen contrast setting to make it more
visible on different environmental conditions.