CHALLENGER SERIES 10‐60 KVA
SAFETY AND WARNINGS
AG–SD‐35 Rev. No:1 Rev. Date:25.09.2013 Publication No:2
9
1.2
Clearance
and
Access
Clearance
There is no any air inlet or outlet grill on the left or right sides of our 10-60 kVA UPS. All air
goes in to UPS from the front and is evacuated from the rear through fans. There must be spaces
at least 1 meter for UPS's front side and 1,2 meter at the back side. Should not be permanent or
temporary use within the limits specified. Otherwise, the UPS performance will decrease.
Access
Operator reaches UPS via front panel on 10-60 kVA UPS. Therefore, enough area must be left for
operator. Also, UPS can be intervened in the back of it for service and maintenance. Because of
this reason , enough area for personal must be left at the rear side of UPS. There is no limit to the
sides of the device.
1.3
Storage
UPS should be kept in a room or area where is protected from excessive moisture and heat before
commissioning..
WARNING:
Unused batteries must be charged at regular intervals. This time interval is determined by the
battery supplier. Charging can be performed periodically by connecting to a proper mains for a
while.
1.4
Shipment
Carrying vehicles must have enough features and characteristics to carry UPS.
Cabinet is equipped with four‐wheel. In this way, it can be placed by moving easily. These
wheels are used only smooth surfaces.
The rear wheels of UPS must be locked after positioning properly.The rear side wheels are
fixed.
Be more careful of sudden movements ,especially when batteries are inside of cabinet.
Move the UPS as rarely as possible.