TRANSFORMER LEVELUPS T3 SERIES 160 - 200 KVA
PRODUCT DESCRIPTION
15
GM-SD-06 / Publication Date: 13.04.2016 Revision No 2 Revision Date 30.01.2017
2.3.1 Advanced Functions (Battery tests) Auto Battery Test
The auto battery test discharges 10% of the battery energy in a user defined period. Default is 90
days. Test reports the battery condition as good, weak or replace. Results of the latest test can be
seen on the battery screen from the status menu.
WARNING: If the test result is “replace”, then
batteries are
completely drained during the test. This may cause the interruption
in the power supply to the critical loads in case of the mains failure.
This test command can be given from front panel monitor, via TELNET interface, via RS232
smart communication or via UPSMAN (SNMP, see the options).
The purpose of the battery test is to check if the batteries can supply the minimum back-up time
needed in case of mains failure. We recommend checking the test results on the regular basis.