TRANSFORMER LEVELUPS T3 SERIES 160
–
200 KVA
OPERATION
34
GM-SD-06 / Publication Date: 13.04.2016 Revision No 2 Revision Date 30.01.2017
WARNING: MAKE SURE THAT THE CABLES ARE CONNECTED PROPERLY
BEFORE UPS İS STARTED. ADDİTİONALY, CHECK İF THERE İS GALVANİC
İSOLATİON TRANSFORMERS AT İNPUT OF UPS AND CONSİDER THE LOCAL
DİRECTİONS.
WARNING: CHECK THE GR
OUNDİNG BEFORE STARTİNG THE UPS. WRONG
WORKS OR GROUNDİNG ON UPS OR OTHER DEVİCES OF İNSTALLATON MAY
BE HAZARDOUS. WRONG WORKS AND GROUNDİNG MAY DAMAGE UPS AND
ANOTHER SYSTEM ON THE İNSTALLATİON.
3.1.5.4 Battery connections
You can find explanations about installation procedures and connections of internal and external
batteries in this section.
3.1.5.4.1 External Battery Installation Procedure and Connection
You can find details about how to configure external batteries above under “External Batteries
C
onfiguration” title.
The information about connection of external batteries and UPS is given in this section.
AVOID SHORT CIRCUITING BATTERIES . SHORT CIRCUIT THE BATTERIES
CAN DAMAGE YOU AND YOUR ENVIRONMENT!
BATTERY TERMINAL MAY RISE UP TO 450 VDC!
1. Switch “CB4”breaker OFF on UPS.
2. If there is breaker on battery cabinet, Switch it “OFF” .
3. Remove the fuse on battery cabinet.
4. Remove battery fuse on UPS.
5. Make sure of serial and parallel connections of external battery packs are correct.
6. Connect the cable to terminals of two neutral "N ( battery neutral)" , one "+Battery" and one
"- Battery" respectively.
7. Connect four cables that come from UPS to terminals on battery cabinet or in battery room
according to external battery connection diagram below. As follows:
➢
N(UPS)
-----
→
Positive Battery Group "-" terminal
➢
N(UPS)
-----
→
Negative Battery Group "+" terminal
➢
“+ BATTERY”
-----
→
Positive Battery Group “+“ Terminal