TRANSFORMER LEVELUPS T3 SERIES 160
–
200 KVA
OPERATION
35
GM-SD-06 / Publication Date: 13.04.2016 Revision No 2 Revision Date 30.01.2017
➢
“
-
BATTERY”
-----
→
Negative Battery Group "-" Terminal
8. Make sure that the polarities are connected correctly by checking battery connections for the
last time.
9. Replace battery fuse on UPS.
10. Replace battery fuse on battery cabinet.
11. If there is breaker on battery cabinet, switch
it “ON”.
12. Check if there is appropriate battery voltages to the battery input terminals by proper
measuring device.
External battery cable selection is determined by application. Fuses which are recommended for
UPS and battery cabinet are given. To connect to these type fuses, the lowest diameter cables are
suggested. Please, refer to standard called EN 50525-2-31(VDE 0100-430) in this subject. The
selection should be such that the cable will allow at most 0.5 Vdc decreasing.
"External Battery Temperature Measurement Kit" is used for optimization according to battery
temperatures, batteries use is optimized according to temperature.
The external battery connection diagram is given below.