TRANSFORMER LEVELUPS T3 SERIES 160
–
200 KVA
OPERATION
39
GM-SD-06 / Publication Date: 13.04.2016 Revision No 2 Revision Date 30.01.2017
4 OPERATION
4.1 Operation Procedure
You can find informations about circuit breaker, first start-up , types of UPS operation tests ,
turning UPS off , EPO and RS232 serial communication system in this section.
4.1.1 Circuit Breakers
There are four circuit breakers on the rear side of the device.
These are used for the AC input, maintenance bypass, output and the battery connections
respectively.
Three-phase AC voltage is applied through
CB1
to input of UPS.
AC input voltage will be applied directly to loads through
CB2
. In this way, maintenance
purposed switching is done properly. If UPS is actived while it is working thanks to auxilary
short circuit info located in CB3, mains makes the bypass static switches actived. The system will
be switched to maintenance mode smoothly.
CB3
is used to connect or seperate AC voltage that come from static switches to the loads on
UPS
.
External batteries are connected to UPS through
CB4.
CB5
is used as an external bypass switch.
Active Brakers
Operation Mode
Explanation
CB1, CB3, CB4.CB5
Normal Mode
UPS operates in normal mode.
CB1, CB3, CB4,CB5
Static Bypass Mode
UPS is overloaded, loads will be transferred to
static bypass line temporarily.
CB2
Maintenance Mode
UPS is shut down for maintanence, loads will be
fed through mechanical bypass line.
4.1.2 First start-up
WAIT FOR AT LEAST 5 SECONDS BETWEEN EACH STEP.
1. Turn all circuit breakers OFF.
2. Push the soft start button (SW1) at least for 10 sec.