POWERPACK PRIME SERIES 1-3 kVA
10
1.
If Line LED flashes, it means that the input may have something wrong, such as input L and N
line reversed or the grounding wire is not connected properly.
2.
If the load level is higher than 100%, the buzzer will beep once every 0.5 second as a warning
for the over-loading condition. The user should remove unnecessary loads one by one, until
the load level become lower than 100%.
3.
If the Battery LED flashes, it means that the battery is not connected or the battery level is too
low. In this case please check the connection of battery and press test button for 2 seconds to
test the battery. If the connection is normal, it’s possible the battery is failed or aged. Please
refer to the common troubleshooting table in chapter
Connecting AC Generator as Input
Remove the loads connected to UPS first. Activate the generator and connect the output of
generator with the input of UPS until the generator operates stably, then turn on the UPS and
add the loads one by one.
Please choose the generator with output capacity which is twice larger than the UPS capacity.
Battery mode
Battery mode means that the battery power goes through the DC/DC section to the inverter
(DC/AC) and output a stable backup power when the mains are failed. If the mains recovered,
the UPS will transfer to line mode without interruption.
In battery mode, Battery LED and Inverter LED are turned on constantly. If Line LED flashes at
the same time, it means that the input mains are abnormal.
1. In battery mode, Buzzer beeps once every 4 seconds. Press test button for 2 seconds in battery
mode, UPS would be muted. To resume the alarm, press test button again for 2 seconds.
2. When the voltage of battery decline to the lower limit, buzzer beeps once every second to
warn the low battery status and remind user to turn off the loads.
3. User may check the backup function by turning on the UPS without connecting the mains
input.