POWERPACK PRIME SERIES 1-3 kVA

 

 

 

 

20 

 

3.5 Charge the batteries 

1.

 

When  the  UPS  is  connected  to  normal  mains,  the  charger  will  start  to  work  and  charge  the 

 

batteries automatically. 

2.

 

It is suggested to charge the batteries for 10 hours at least before the UPS performs battery 

 

mode. Otherwise the backup time may be less than the expected value. 

3.6 Discharge the batteries 

1.

 

When  the  UPS  is  in  battery  mode,  the  buzzer  will  start  beep  according  to  different  battery 

 

level.  If  the  battery  voltage  drops  to  the  alarming  level,  the  buzzer  will  start  beep  rapidly 

 

(once every sec) to remind the user that the capacity of battery is too low and the UPS will be 

 

shutdown  automatically  soon.  The  user  may  switch  off  some  non-critical  loads  to  avoid  the 

 

shutdown  alarming  and  prolong  the  backup  time.  If  no  more  non-critical  loads  can  be 

 

switched  off  at  that  time,  it’s  better  to  shut  down  rest  loads  as  soon  as  possible  to 

 

protect the important loads or save data. Otherwise there might be a risk of data loss   or 

 

damage loads by power interrupted after  batteries discharged.  

2.

 

If  the  user  found  the  buzzer  is  noisy  under  battery  mode,  the  beep  could  be  muted  by 

 

pressing the test button for 2 seconds.  

3.

 

The backup time may vary from different environmental temperature and load type. 

3.7 Test the batteries 

1.

 

The  user  may  check  the  battery  level  or  aging  status  when  the  UPS  is  under  normal  mode 

 

(line mode) by pressing test button for 2 seconds to enter battery test mode. 

2.

 

To make the system more reliable, the UPS will automatically perform battery test on regular 

 

basis. The default period is once per 90 days. 

3.

 

The battery test could be performed by sending command from monitoring software through 

 

the communication port. 

4.

 

If  the  UPS  enters  the  battery  test  mode,  the  buzzer  will  beep  once,  and 

 

Line/Bypass/Inverter/Batter  LEDs  will  be  on  and  off  one  by  one,  which  allows  the  user  to 

 

check the battery level in this mode. 

3.8 Turn off the UPS with mains (AC source) 

1.

 

To turn off the UPS, please press the ON/OFF button continuously for more than 1 second. 

2.

 

After pressing the button, UPS will have no output. If the mains power is normal, the Line LED will 

 

turn  on.  If  there  is  no  mains  power,  10  seconds  later,  the  numeric  area  of  LCD  display  will  be 

 

lighted in sequence, finally all the LCD and LED will be blackout, and UPS shutdown completely. 

 Note 

1: 

If the UPS’s bypass mode is enabled, the output socket will still have voltage directly from 

 

mains power after switching the UPS off. 

 Note 

2:

 There is a risk of power interruption for the loads if the UPS works in bypass mode. 

3.

 

To  turn  off  the  output  of  UPS  and  shut  down  the  UPS  completely,  it  is  recommended  the  mains 

 

power of UPS shall be disconnected. 

 Note: 

please make sure all the loads are prepared or turned off before shutting down the UPS. 

Summary of Contents for POWERPACK PRIME SERIES

Page 1: ...USER MANUAL POWERPACK PRIME SERIES 1 3 KVA...

Page 2: ...UDD SD 113 Release Date 26 12 2014 Rev No 0 Rev Date 1...

Page 3: ...VA UDD SD 113 About The Manual This manual is prepared for the users of Powerpack Prime Series 1 3 kVA Companion Manuals For further information about this device and its options please visit www make...

Page 4: ...cification 13 1 6 Communication Port 14 1 6 1 RS232 14 1 6 2 Intelligent Card 14 2 INSTALLATION 15 2 1 Safety Instructions for Installation 15 2 2 Unpacking and Inspection 16 2 3 Installation Steps fo...

Page 5: ...MAINTENANCE 22 4 1 Maintenance Safety Instructions 22 4 2 Typical Troubleshooting 24 4 3 Battery Maintenance 25 4 4 Contact the service centre 26 5 TRAMSPORT and STORAGE 26 6 STANDARDS 26 7 GUARANTEE...

Page 6: ...ble si ome abnorm y to make su back to nor always pow ternal bypas or failed an internal c onable range UCTION conversion load such a ut AC curren ctor system ne wave AC mal the con ure the DC A rmal...

Page 7: ...POWERPACK PRIME SERIES 1 3 kVA 6 1 2 Front Panel 1 2 1 Front View 1K 2K 3K 1 2 2 LCD and LED Display...

Page 8: ...on UPS UPS would send a beep to indicate the power on status Turn off UPS Press ON OFF button for 1 second to turn off UPS when UPS is in line mode or battery mode Clear fault status Press ON OFF butt...

Page 9: ...POWERPACK PRIME SERIES 1 3 kVA 8 1 3 Rear panel...

Page 10: ...Mode description Line mode Line mode means that the mains input is rectified converted by the AC DC section and then inverted to stable output by DC AC section In line mode the output is well regulat...

Page 11: ...the output of generator with the input of UPS until the generator operates stably then turn on the UPS and add the loads one by one Please choose the generator with output capacity which is twice larg...

Page 12: ...n is not cification cription applicable to 1K 1000VA 8 B 3 kVA UPS provide n If the cont The bypass re tool Bypass LED s that the in nding wire is Ds is the sam t enabled un o the follow 00W 2000V Byp...

Page 13: ...rage Temperature 25 55 C Altitude 1000m full load 2000m 91 load 3000m 82 load 4000m 74 load Relative Humidity 20 90 Noise Level 45dB 1 meter from front panel 50dB 1 meter from front panel 1 5 3 Mechan...

Page 14: ...05 Hz battery mode Voltage Regulation 2 Overload Capacity 47s 25s linear 105 150 25s 300ms linear 150 200 200 200ms Efficiency Line Mode 89 90 90 Battery Mode 83 83 83 Battery Charger 25C Total batte...

Page 15: ...Card Intelligent card AS400 card NMC card and CMC card are optional The intelligent card is inserted into intelligent card slot a AS400 card Monitor the UPS by using the AS400 management function if...

Page 16: ...UPS cold enviro erated Plea hock may exi n the environ PS is far awa nts on the ho enough spac must be pe rely ground s have the eq wire and out device as t mains stalled only ty instructio afety ins...

Page 17: ...muni mmunication he guide ma nagement m 3 kVA ciple of sam t be used as of protectio ion eck the cont he UPS to se dealer imm ndard Mode uit breaker c shock and h in the build rned on befo re connecti...

Page 18: ...or fire c following s s designed t 3 kVA uctions earth wire o would resu semble the he mains po t may be ele urce r foreign obj put switch a closed to the afety instru to be opera on the UPS o ult in...

Page 19: ...ers line mode normally the Inverter LED will be on the Bypass LED and Battery LED will be off There will be no beep from buzzer 3 Press the battery test button for 0 5 second UPS will show the informa...

Page 20: ...oads one by one 1 If it is necessary to connect the inductive load such as a printer to the UPS the start up power should be considered for determining the capacity of the UPS because the power consum...

Page 21: ...1 The user may check the battery level or aging status when the UPS is under normal mode line mode by pressing test button for 2 seconds to enter battery test mode 2 To make the system more reliable...

Page 22: ...F button continuously for more than 1 second 2 After pressing the ON OFF button the buzzer will sound beep once The numeric area of LCD display will be lighted in sequence finally all the LCD and LED...

Page 23: ...pa PS ect the batte y result in el between th In this pro tages may o rdous volta r y wristwatc ulated grips afety instru ntained onl d to the ma acitor insid eries before lectrical sho he battery te...

Page 24: ...ed when wo s or other m ed handles nd boots tal parts on ng source pr y is inadver Contact with of such sho tenance ap pply circuit negative of t cause a risk replace th batteries by deposed acc tteri...

Page 25: ...arning Line abnormal Input line abnormal wait for line resume A07 Beep every 2 minute L N connection reverse Please check L N and the ground connection is OK A08 Decide by other warning Bypass abnorma...

Page 26: ...usly beep Inverter capacitor open 4 3 Battery Maintenance 1 The battery used for standard models are valve regulated sealed lead acid maintenance free battery It shall be charged regularly in order to...

Page 27: ...information for complete description of the problem 5 TRAMSPORT and STORAGE Please transport the UPS only in the original packaging The UPS must be stored in the room where it is ventilated and dry 6...

Page 28: ...having similar features for the use of consumers until the faulty product has been repaired Even though consumers exercise their repair rights they can claim free replacement of products refund or pri...

Page 29: ...code serial number belonging to the product be on the product Otherwise it is not covered in the scope of the guarantee It is essential that products to be sent through freight definitely be together...

Page 30: ...reakdowns resulting from treatments internally or externally tampering efforts to repair and spare part replacement of products without approval of MAKELSAN and those resulting from treatment of unaut...

Page 31: ...PERIOD 20 business days GUARANTEE PERIOD _______________________________________________ VENDOR TITLE _______________________________________________ ADDRESS __________________________________________...

Page 32: ...the product repeats the same malfunction more than twice or different malfunctions occur more than four times in a year starting from the delivery date on the condition of being in guarantee period Th...

Page 33: ...956 Tuzla stanbul Tel 0216 428 65 80 Fax 0216 327 51 64 E mail makelsan makelsan com tr zmir Office Halkap nar Mah 1348 Sok 2AE Keremo lu Merkezi Yeni ehir zmir Tel 0232 469 47 00 Fax 0232 449 47 00 E...

Page 34: ......

Page 35: ......

Page 36: ...Fax 0216 327 51 64 E mail makelsan makelsan com tr zmir Office Halkap nar Mah 1348 Sok 2AE Keremo lu Merkezi Yeni ehir zmir Tel 0232 469 47 00 Fax 0232 449 47 00 E mail izmir makelsan com tr Ankara O...

Reviews: