POWERPACK PRIME SERIES 1-3 kVA
7
LED definition
There are total 4 LEDs to indicate the status of UPS.
Name
Colour
Function
Bypass LED
Orange
To indicate that the UPS is in bypass mode, and the load
current is directly from the mains power.
Line LED
Green
To indicate that the mains input is normal.
Inverter LED Green
To indicate that the load current is supplied from the mains
power or battery via the inverter.
Battery LED
Orange
To indicate that the UPS is in battery mode, and the load
current is from battery via the inverter.
1.2.3 Button
(1) ON/OFF button
Turn on UPS
Press ON/OFF button for 1 second to turn on UPS. UPS would send a
beep to indicate the power-on status
Turn off UPS
Press ON/OFF button for 1 second to turn off UPS when UPS is in line
mode or battery mode.
Clear fault status
Press ON/OFF button for 3 seconds to clear the fault status of UPS.
(2) Test button
Battery test
In line mode, press test button for 2 seconds to test the battery.
Mute in battery
mode
Press test button for 2 seconds in battery mode, UPS would be muted.
To resume the alarm, press test button again for 2 seconds.
Mute in all mode
Press test button for 10 seconds, UPS would be muted. To resume the
alarm, press test button again for 10 seconds. The key tone and
battery voltage under alarm (every second buzzer beep twice) cannot
be muted.
Page up/down
Press test button for 0.5 seconds, UPS would turn from main menu to
sub-menu in sequence