UDD-SD-116/
Release Date: 31.12.2014/Rev No: 1/Rev.
Date
: 27.04.2015
44
Rated input voltage
220V
Rated input frequency
50Hz/60Hz auto-adaptive
Input voltage range
(115
~
295)±5VAC (half load); (165
~
295)±5VAC(full load)
Input frequency range
40
~
70Hz, ±0.5%
Input current
46A max
76A max
PFC
≥0.99
THDI
﹤
5%
Bypass voltage range
160V
~
Rated output v32V
Output
Output voltage
220V
208VAC/220VAC/230VAC/240VAC Setting available via LCD
120V
100/110/115/120VAC Setting available via LCD
Output PF
0.9
Output power(Watt)
5400
9000
Inverter overload capability
105%
~
125%: 3 mins; 125%~150%: 30 secs;
>
150%: 100ms;
Voltage accuracy
±1%
Load crest
3:1
From AC mode to BAT mode
0ms(transfer time)
From BAT mode to AC mode
0ms(transfer time)
Efficiency
Line mode
≥92%
BAT mode
≥91%
ECO mode
≥98%
Output frequency
Line mode
Same as input frequency
BAT mode
(50/60±0.2)Hz
CUCF mode
(
50/60±0.2Hz
Phase-locked rate
≤1Hz/s
Total voltage harmonic
distortion
Full linear load< 2%
;
Full nonlinear load< 5%
Battery
Battery type
Sealed lead acid maintenance free battery
Quantity
16
DC voltage
192V
Charger output voltage
216.8±1V
Inbuilt battery
7AH/12V
9AH/12V
Charge method
Three-stage charging
Back up time
Based on battery capacity
Charge current
Standard model:1A
Long-run model: 1A /3A /5A /8A
System Control and Communication
Function
Silence; cold start; AC restart; Auto restart.
Protection
Over-temp protection; Fan testing protection;
AC L and N reversely connecting protection;
Output short circuit protection
Communication port
RS232; SNMP card; USB; Dry contact