background image

8189 Century Boulevard • Minneapolis, MN 55317-8002 • USA

800-843-5116 • 952-556-4900 • Fax 952-556-4997
sales@mamacsys.com  •  www.mamacsys.com

Installation Instructions

IS.EP311/313-08

ELECTROPNEUMATIC TRANSDUCER

For Additional Information See EP 311/313 Data Sheet

ORDERING INFORMATION

Inspection: 

 Inspect the package for damage.  If damaged, notify the

appropriate carrier immediately.  If undamaged, open the package and

inspect the device for obvious damage.  Return damaged products.

Requirements:

  

Installer must be a qualified, experienced technician.

  Tools 

(not provided)

:  

-  Digital Volt-ohm Meter (DVM)

-  Appropriate screwdriver for mounting screws

-  Appropriate drill and drill bit for mounting screws

  Appropriate accessories

  Three #8 self-tapping mounting screws (not provided)

Warning:

  Do not use on oxygen service, in an explosive/hazardous environment, 

    or with flammable/combustible media.

  Disconnect power supply before installation to prevent electrical shock 

    and equipment damage.

  Make all connections in accordance with the job wiring diagram, and in 

    accordance with national and local electrical codes.  Use copper  

    conductors only.

Caution:

  Use electrostatic discharge precautions (e.g., use of wrist straps) during

    installation and wiring to prevent equipment damage.

  Do not exceed ratings of the device.

Mounting:  

The EP-311/313 must be mounted in an upright position so that the

ports are facing upward and the gauge can be easily read.

 

1. 

 

Select the mounting location.

2.  

Mount the transducer on a vertical surface with three #8 self-tapping screws 

(not provided).

3.  

Pull wires through the bottom of the device and make necessary connections.

4.  Make the necessary pneumatic connections.

Wiring:

  Use maximum 12 AWG wire for wiring terminals.  Use flexible 1/4”

O.D. poly tubing for main and branch pneumatic connections.  Refer to

Figure 1

 and 

Figure 2

 for wiring configurations, 

Figure 3

 for terminal

location and designation, and 

Figure 4

 for dip switch settings. 

CAUTION!

  

Main supply pressure must not exceed 40 PSIG.

  A minimum of 6 to 10 feet (1.8 to 3.0m) of tubing should be between the unit

   and the actuator.

  For 24 VAC supply voltage, ensure that the hot and neutral are not reversed.

   If more than one unit is being powered from the same transformer, the hot

   and neutral should be the same for each unit.

Note:

  

The gauge on the unit is for indication only.  The transducer’s calibration 

is more accurate than the accuracy of the gauge.

Figure 1

 - 

Wiring Diagram for 24 VAC Supply Configuration

Figure 2

 - Wiring Diagram for 24 VDC Supply Configuration

TYPICAL APPLICATIONS (wiring diagrams)

SPECIFICATIONS

Accuracy*: 

  ± 1% FS

Maximum Supply Pressure:  

40 PSIG

Pressure Differential:  

0.1 PSIG (supply to branch) 

Supply Current:  

150 mA

Enclosure:  

18 Ga. C. R. Steel Chassis

Finish:  

Baked on enamel - PMS2GR88B

EMC Conformance:

 

EN 55022, 55024, 61000-3-3,

   

  

     61000-4-2, 3, 4, 5, 6 & 11

Compensated Temperature Range:  

25°F to 150°F (4°C to 65°C)

 

T. C. Error:  

± 0.025%/°F (.03%/°C)

:

Media Compatibility:  

Clean dry air or any inert gas

Port Connection:  

1/4" O.D. poly tubing

Environmental:  

10 - 90% RH non-condensing

Termination:  

Screw terminal block

Wire Size:  

12 Ga. max.

Input Impedance:  

301 ohms (4-20 mA)

                               10K ohms (0-5/0-10 VDC)

Weight:  

1.0 lb. (.45 kg)

* Includes non-linearity, hysteresis and non-repeatability

Supply Voltage:  

18-28 VAC/VDC

INSTALLATION

Caution:  

This product contains a half-wave rectifier power supply and 

must not be powered from transformers used to power other devices 

utilizing non-isolated full-wave rectifier power supplies.

RoHS

Reviews: