Email Alerts:

 If an email alert is desired on input # 1, please enable by clicking the radio 

button. Enter the desired lower and upper values for the alert and click on the down arrow to 
unable or disable the alert. For example, if you would like an email alert if the temperature goes 
above 76°F and back to 

Normal

 if it goes below 74°F; enter 74°F in the lower field and click 

Alert Disabled

, and enter 76°F in the upper field and click 

Alert Enabled

. In order to filter 

out false alarms, the input has to be in the alert state for more than one second (default) before 
the Maverick sends out an alert email. If this filter time needs to be increased, click the down 
arrow and pick the desired filter interval. If logging is enabled on this input and if the user 
desires the Maverick to attach the log to the email, please click the 

On

 radio button for 

Attach 

Log

 field. Default is 

Off

Email alert is now configured and if the sensor variable goes above the upper value in the above 
example, an email alert will be transmitted to the email address(es) specified on the 

Email

 

Configuration

 page after the programmed filter interval has lapsed. A CSV log will also be 

attached if the user has specified. Similarly, if the user desires the Maverick to send an email if 
the sensor value goes below 74°F in the above example and returns to normal if above 76°F 
(heating alert), just switch 

Alert Disabled

 in the 

Lower Value

 to 

Alert Enabled

 and switch 

Alert Enabled

 in the 

Upper Value

 to 

Alert Disabled

.

Output Control:

 Any input can also do setpoint control on any output. To enable 

Output 

Control

 click the down arrow to the desired output number. 

Default is 0

, no control. In the 

above example, if the user would like relay/output 1 (heat) to come on if the sensor value goes 
below 74°F, enter 

74.0

 in the 

Lesser than or equal to

 field and click  the down arrow and 

pick 

Relay On

. Next enter 

76.0

 in the 

Greater than or equal to 

field and click the down 

arrow and pick 

Relay Off

. Control is programmed. If the sensor variable goes below 74°F, 

output 1 will switch on and when the sensor value heats up to 76°F, the relay will switch off. In 
this way, the user can define the deadband or hysteresis for each input independently.

On the other hand, if the user would like the above to cool if the sensor input goes above 76°F 
and shut down cooling if the input goes below 74°F; just switch the 

Relay On

 to 

Relay Off

 in 

the 

Lower Field

 and 

Relay Off

 to 

Relay On

 in the 

Greater Than

 field. 

Click 

Save

. Configure each sensor input. If no sensor is connected to an input, please leave 

the values in all fields for that sensor at default.

2.5.5

2.5.6

© Copyright 2008

DN IS-IPPC101.1

® Registered trademark MAMAC SYSTEMS, Inc.

12 of 20

SECTION 2 - Sensor Inputs, Email Alert & 

Setpoint Control Configuration

Summary of Contents for Maverick IP-PC-101-44-VDC

Page 1: ...Fax 01384 271114 4 Arminger Court Unit 2 Holden Hill S A 5088 Australia 08 8395 4333 Fax 08 8395 4433 155 McIntosh Drive Units 5 6 Markham Ontario L3R ON6 Canada 905 474 9215 Fax 905 474 0876 No 22 Lo...

Page 2: ...Configuration DHCP IP 3 1 0 Main Page 3 1 1 Manual Control 3 1 2 Data Logging 3 2 0 Reset Button 3 3 0 XML Page 15 Page 16 Page 17 Page 18 Page 19 Page 20 Page 20 SECTION 2 Initial Configuration Page...

Page 3: ...rbances induced by radio frequency fields EN 61000 4 11 Voltage dips short interruptions and voltage variations immunity test 1 0 1 RoHS Compliant MAMAC Systems Inc products designated RoHS Compliant...

Page 4: ...nce without any training or support in less than 5 minutes due to the innovative and familiar web browser based configuration The Maverick is an ideal low cost solution for light commercial residentia...

Page 5: ...C VDC Neutral Com Ground Earth Input 1 Common Common Common Common Input 2 Input 3 Input 4 Out 1 NC Out 1 NO Out 1 COM Out 2 NC Out 2 NO Out 2 COM Out 3 NC Out 3 NO Out 3 COM Out 4 NC Out 4 NO Out 4 C...

Page 6: ...4 50 3 60 4 00 3 70 MAMAC SYSTEMS 4x 0 156 use 6 sheet metal screws not included to mount appliance 114 mm 91 mm 102 mm 94 mm Figure 2 Warning Caution Disconnect power supply before installation to pr...

Page 7: ...ommon must terminate at the transformer power supply neutral common Digital inputs are terminated as shown in fig 4 MAMAC SYSTEMS Figure 4 Digital Input 2 Digital Input 1 WARNING Digital Input must no...

Page 8: ...output terminal blocks and leave only the power terminal block plugged in Attach the crossover cable to the appliance and the other end to the laptop ethernet jack as shown in fig 5A If using a hub a...

Page 9: ...wn in fig 6 Example 192 168 1 XX The XX can be any number except 10 because the Maverick default IP is 192 168 1 10 We recommend using 192 168 1 11 Now click on the second line Subnet mask It should a...

Page 10: ...liance mamacsys com DHCP Network Configuration Dynamic Host Communication Protocol is used if a static IP is not available To configure the appliance as DHCP click the DHCP Enabled radio button Please...

Page 11: ...the default password and username Current time date firmware version and MAC address is displayed on the Password Clock page for reference purposes Node I D Please fill in the name of the appliance i...

Page 12: ...ue would be 30 Default value is 0 Max Value Enter the maximum value for the sensor range in this field For the above examples the maximum value for 0 to 100 F would be 100 and for 30 to 130 F would be...

Page 13: ...low 74 F in the above example and returns to normal if above 76 F heating alert just switch Alert Disabled in the Lower Value to Alert Enabled and switch Alert Enabled in the Upper Value to Alert Disa...

Page 14: ...s only controlled by a sensor input no additional configuration is required If time based control is desired on an output please click Enabled default is Disabled Click the radio button On for each da...

Page 15: ...t CAUTION For accurate data please make sure clock time is configured correctly before initiating logging Enable and configure logging for each input desired Digital inputs can be logged also if the a...

Page 16: ...t the Maverick to the ethernet as shown in fig 7 Three options are available 1 Use a CAT 5 patchcord and plug it into a hub or switch and connect the hub switch to a router on the web 2 Use a CAT 5 ca...

Page 17: ...o the Bridge with a CAT 5 cable For more information on wireless 802 11 B G configuration please refer to AN IP802 11 Terminate the sensors and outputs as shown in fig 3 Section 1 4 1 Power up the app...

Page 18: ...a alert state the appropriate field will change from Normal to Alert in red color Similarly if an output is in manual mode the field will change from Automatic to Manual in red color 13 34 59 May 9 2...

Page 19: ...back to automatic click Manual Control on the navigation bar change the state to Off and click Save Again click the Automatic radio button and hit Save Output is back under automatic control CAUTION...

Page 20: ...elect Graphs and click the desired Input The Maverick will initialize a JAVA script and graph the data To refresh the graph click Update Graph If the user would like to narrow the X scale sensor value...

Page 21: ...encoding ASCII Maverick xmlns http mamacsys com mav NodeID MAMAC3 NodeID CurrentTime 13 31 25 CurrentTime CurrentDate September 26 2008 CurrentDate Sensor Channel 1 SensorName Boiler Temp SensorName...

Reviews: