INSTALLATION REQUIREMENT
1.Roof installation requirement
The Mammoth Fan must be installed in a location so that the blades have enough space between the and the nearest objects or
walls (Refer to the below diagram for detail spacing requirement).
Secure the hanging bracket to the ceiling joist or structure with bolts & nuts provided. Ensure there are 3 – 4 threads left on the
bolt after tightening the nut.
The structure to which the fan is to be mounted must be capable of supporting 2 times the weight of the product and its own
structural loading. Check with a structural engineer if unsure.
2. I-Beam Steel structure
(Included as standard)
Extension tube
0 - 5.2M
Driving unit
0.36M
≥0.5M + R if the object is
lower than the fan blade
≥0.5M if the object is at the
same level as the fan blade
≥0.5M if the object is
above the fan blade
Roof
R
Ground
≥3.5M
NOTE: be cautious of items like light fittings which may swing into the
path of the spinning fan, ensure appropriate clearance is maintained.