Installation and Commissioning
43
Carefully read the Operating Instructions before starting any work!
This is especially valid for the chapter on General Safety Instructions
and the safety instructions in each of the chapters.
S
For safety reasons we recommend placing an off limits sign on the door to the engine room and to in
struct the operating personnel that they are responsible for the safety of people who enter the engine
room.
6.3
Installation - Engine
The installation of the engine, i.e. connection to the power supply, connection of the cooling system, are to
be performed in accordance with the manufacturer's instructions for the entire system and with the help of
the “Assembly Instructions”.
6.3.1
Safety Equipment
WARNING!
Risk of death caused by the absence of safety equipment!
An emergency-off button, for shutting down the system or engine in an emergency, must be
installed for each engine.
For this reason:
S
Install an emergency stop button to shut down the system in an emergency.
S
Check whether all of the safety equipment is correctly installed and in good operating or
der.
WARNING!
Risk of death caused by faulty operation!
At excessive loads or if malfunctions occur the engine can overheat and suddenly seize.
For this reason:
S
The sensors which monitor the engine parameters must be connected to and evaluated
by the module manufacturer's monitoring equipment.
S
If sensor values go outside the permissible limits or if there is a power loss, the engine
must be able to be immediately shut off by the monitoring equipment.
The following sensors are installed in the engine:
S
Exhaust temperature
S
Oil pressure
S
Coolant temperature
6.3.2
Engine Model Plate Data
Please always specify the engine model, engine number and order number when corresponding with MAN,
see page .
For this reason, before commissioning the engine, read off the data from the engine model plate and enter
it into the Engine Model Plate chapter, see page 25.