Electrical system
60
Battery size and starter cable
Starters
Mitsubishi 105P70
Battery capacity
Ah
140
155
175
200
225
Battery current as per DIN 43539
A
460
540
540
630
680
Battery current as per DIN EN 50342 A
760
900
900
1050
1150
Battery resistance at 20°C
m
Ω
5.8
5.5
5.3
5.0
4.7
Permitted battery cable resistance (positive
and negative cables) with
contact resistance
m
Ω
min
0.4
max.
4.9
min
0.7
max.
5.2
min
0.9
max.
5.4
min
1.2
max.
5.7
min
1.5
max.
6.0
Starter short−circuit current at 20°C
A
2370
1620
2370
1620
2370
1620
2370
1620
2370
1620
Minimum starter cable diameter
mm
2
79.0
54.0
79.0
54.0
79.0
54.0
79.0
54.0
79.0
54.0
Cable diameter
mm
2
Cable resistance (Cu)
m
Ω
/m
Minimum/maximum cable length (total length for positive and negative cables) in meters
min.
max.
min.
max.
min.
max.
min.
max.
min.
max.
35
0.53
Current is too high
50
0.37
70
0.26
4.5
16.9
5.6
18.1
6.4
18.9
7.6
20.0
8.7
21.2
95
0.20
22.4
1.1
23.9
2.1
25.0
3.6
26.5
5.2
28.0
120
0.15
28.7
1.4
30.7
2.7
32.0
4.6
33.9
6.6
35.9
140
0.13
33.8
1.6
26.1
3.1
37.6
5.4
40.0
7.7
42.3