26
Built-in Cycle Counter
The Electronic Control Board includes an internal non-resettable cycle counter. E
ach complete door cycle is counted
and the value is stored in the internal memory of the control board, providing valuable data for maintenance
scheduling.
Cycle Counter Display
Select Switch
1. Verify if the close limit switch is activated and if the close LED is ON.
2. Set select switch on
E
.
3. Wait until all 3 Indicator LEDs have turned OFF:
GREEN (D2), RED (D3) and ORANGE (D4).
4. Press the “Open” button to activate the Cycle Counter Display
Sequence. The 3 Indicator LEDs will FLASH in order to display the #
of cycles as follows:
•
ORANGE LED (D4)
a
# of 100K cycles
•
RED LED (D3)
a
# of 10K cycles
•
GREEN LED (D2)
a
# of 1K cycles
Ex: 205 000 cycles or 205 999 cycles will be displayed the same:
•
ORANGE LED (D4)
a
will FLASH
2
times (
2
00 000);
•
RED LED (D3)
a
will FLASH
0
times (2
0
0 000);
•
GREEN LED (D2)
a
will FLASH
5
times (20
5
000)
Note: Quantities under 1000 cycles are not displayed.
5. During the Cycle Counter Display Sequence, pressing the “Stop”
button will stop the 3 Indicator LEDs from flashing. Pressing the
“Open” button once again, will commence the Counter's Display
Sequence.
6. Set select switch run mode (
0, 1, 2, 3, 4 or 5
).
Refer to Run Mode Settings section, p. 24 for mode descriptions.
Indicator LEDs
Cycle Counter Display Sequence
Mid Stop (MD STP)
NOTICE
•
The Mid-Stop position must always be programmed/adjusted so that there is a minimum gap of 12”
between the top of the tallest vehicle and the bottom edge of the door.
Mid-Stop, when activated, will allow the door to stop at a predetermined position when an open signal is given from
the fully closed position. The Radio control or Close push-button will close the door from the mid-stop position. The
door will open fully from mid-stop position if the Open button is activated.
Mid-Stop Activation
Select Switch
Mid-Stop Deactivation
1. Verify if the close limit switch is activated and
if the close LED is ON.
2. Set select switch on
C = MdStP
.
3. Press the “Open” button. While door is
moving press “Stop” button at desired (mid-
stop) position.
4. Set select switch on run mode
(0, 1, 4, or 5)
.
1. Verify if the close limit switch is
activated and if the close LED is ON.
2. Set select switch on
C = MdStP
.
3. Press the “Stop”, “Close” and “Open”
buttons consecutively.
4. Set select switch on run mode
(0, 1, 2, 3, 4 or 5)
.
For technical support, please call
1-800-361-2260
for more information
D2 (GREEN LED):
# of 100K cycles
D3 (RED LED):
# of 10K cycles
D4 (ORANGE LED):
# of 1K cycles
Summary of Contents for MSJ
Page 1: ... 00 111 ...
Page 3: ...1 A A C D 8A A 9 8 8 77 877 A8778A A A 8 E 0 1 0 E F E 2 4 0 7 9 0 0 0 5 6 E 66 12 26 00 111 ...
Page 35: ...1 L A A C D 8A A 9 E 0 0 C 7D 8A 8 3878 S 0 8 E 0 7 A 0 A A 7 6 A S 8 L S L 6 6 7 3 00 111 ...
Page 37: ...14 A D 8A 9 3 0 A 00 111 0 3 0 7 3 3 3 0 5 ...
Page 52: ...Reg T M of 9141 0720 Québec Inc BOOK 1029 REV 0 2019 09 06 ...